The AW letterbug and the CP image name must be the same. That is, if the AW is AW0001, the CP image will be AW001 in things like = the Select display. Regards, Alex Johnson Invensys 10707 Haddington Houston, TX 77063 713.722.2859 (office) 713.722.2700 (switchboard) 713.932.0222 (fax) ajohnson@xxxxxxxxxxx <mailto:ajohnson@xxxxxxxxxxx>=20 For the latest information on ArchestrA, go to www.invensys.com/Archestra.html <http://www.invensys.com/divisions/Archestra.html> . -----Original Message----- From: Ashley Davey [SMTP:Ashley.Davey@xxxxxxxxxxxx] Sent: Monday, January 20, 2003 5:14 AM To: foxboro@xxxxxxxxxxxxx Subject: Re: [foxboro] AW51EX config Hi,=20 Here is an extract from the FOXDOC=20 B0193JG, Rev H, Chapter 2. Software Installation Procedures=20 =AF-----------------------------------------------------------------=20 To use the set_letterbug utility:=20 Boot the AW in a stand-alone mode.=20 Enter the VT100 local environment.=20 Type the following (where <LBUG> is the desired letterbug): /usr/local/set_letterbug <LBUG>=20 When the AW is booted while connected to a DNBI/DNBX, it automatically assumes the letterbug in the DNBI/DNBX, overriding any letterbug set with the set_letterbug utility. If an AW is booted = stand-alone after having been booted connected, it retains the letterbug it assumed = when booted connected until the set_letterbug utility is run again.=20 If a stand-alone AW is to be connected to the Nodebus, it must be rebooted after the physical connection is made. This allows the = operating system to confirm that the letterbug (contained in the DNBI/DNBX) is = unique within the system. An AW connected to the Nodebus without rebooting = does not communicate on the Nodebus. ********************************* Regards Ashley Davey Software Engineer African Products (Pty) Ltd Gauteng, RSA Tel : +27 11 458 5342 Fax : +27 11 458 5343 >>> Jean-Christophe.MUTI@xxxxxxxxxxxxxx 20/01/03 11:32:28 AM >>> Hi list, Does anybody knows how to configure a particular name for the Xcontroller. Example my station (aw51x) has a name PCAT00 (default name). But i don't want to have the same name for the controller. By default it is the same. Any ideas ? thank u all -- No attachments (even text) are allowed -- -- Type: image/gif -- File: guy1.gif -- No attachments (even text) are allowed -- -- Type: image/gif -- File: jctalk.gif =09 _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave WARNING: This e-mail is being sent from African Products (Pty) Limited, and is intended for the addressee named above. Any = unauthorised use or interception of this e-mail is illegal. The e-mail message or its attachments may contain confidential or privileged information and may = not be copied, forwarded or disclosed to any unauthorised person. If you = are not the named addressee (or person responsible for forwarding the e-mail to = the addressee) please notify us immediately via return e-mail and destroy = the copy you have received. Save for bona fide company matters, African = Products (Pty) Limited accepts no responsibility for the opinions or the content = in this e-mail or its attachments. =20 =20 =09 _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html =20 foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave =20 _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave