Hi!
Last year we faced some problems at nodebus involving AW freezing. The
problems were credited to our high nodebus traffic level (it was about
1000pcg/sc). After some work the traffic became about 600pcg/sec. Now I'm
trying to monitor nodebus traffic in order to prevent further problems.
We have a routine based on remv and remd commands witch resets the counters
once every day.
Our system consists of 10 CPs (6 of them are FT), 3 AWs, 4 WPs and 9
Gateways, everything in a single node. In the middle of the nodebus we have
NCNI modules (they replaced our old FONBEs).
I am trying to have an idea of the rate of frames transmitted for each
station. The numbers I got are:
AWs: about 6.500.000 frames transmitted / day;
WPs: about 1.000.000 frames transmitted / day;
CPs: about 3.500.000 frames transmitted / day;
MG: about 1.000.000 frames transmitted / day;
Are those rates OK or they are too high for a single node application? We
are thinking about splitting the nodebus in two in order to reduce the
traffic level...
Thanks,
Rogério Weber kirst
Evaluation Engineering
COPESUL
Tel: 55 51 457-6040
Fax: 55 51 457-6008
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
Other related posts:
- » [foxboro] nodeus traffic