Re: [foxboro] remote DM's on multi-headed machine
- From: Brian Bates <batesb@xxxxxxxxxxx>
- To: foxboro@xxxxxxxxxxxxx
- Date: Thu, 29 Apr 2004 08:28:28 -0400
GOPS
I am setting up a W2000 machine running "terminal services", and exceed 9.0
for terminal services.
This will enable us to remotely start a virtual PC on your PC (similar to
VNC).
Like VNC, for every terminal that is started up the display number is
incremented. :0, :1, :2, etc.
This works fine with DM's that are unassigned in dmcfg, I can get a DM on
:0, :1.:2 etc.
When I assign the machine name of the "terminal server", it can get a DM
only on :0.
The comments at the top of the dmcfg file show to use the following:
.0 for the primary (local) head
.1 for second (local) head
.- for either local head
xxx Xserver name of remote terminal
$screen_variable user-defined SCREEN variable
- any monitor (undedicated DM)
With $screen_variable configured with the SCREEN section properly
configured, only the primary head :0 works.
With "-" configured, *ALL* of the terminal sessions can call up DM's.
...I need to be able to call up specific DM's on this machine.
I tried to combine "screen_variable" and ".-" and used "screen_variable.-",
but with this config. the DM would not work on any machine.
-Brian
gop@xxxxxxxx
Sent by: To: foxboro@xxxxxxxxxxxxx
foxboro-bounce@fr cc:
eelists.org Subject: Re: [foxboro] remote
DM's on multi-headed
machine
04/29/2004 12:40
AM
Please respond to
foxboro
Brian,
What are you using to emulate the X-Windows ? Exceed or VNC ? Or are you
justsharing X-Windows across WP's ?With VNC, this works in a different way,
because you can start several server sessions on the same machine and the
endusers can open remote desktop instances :0 or :1 etc .
While using Exceed Emulation or other WP's to share DM's, you are actually
exporting the DM to that machine . You should have additional DM licenses
configured in the host machine . And the names of every DM has to be
defined
in the dmcfg file ( either floating or with a dedicated station alias name
).
Hope this helps.
GOPS
----- Original Message -----
From: Brian Bates <batesb@xxxxxxxxxxx>
Date: Wednesday, April 28, 2004 10:19 pm
Subject: [foxboro] remote DM's on multi-headed machine
>
>
>
>
>Hi all
>
>Does anybody out there know how to configure the dmcfg to allow
>remote DM's
>on multiple heads of a remote host?
>If a DM is unassigned, then I can start remote DM's on :0, :1 :2
>etc. ...
>no problem.
>
>If I assign the DM to a specific machine, then I can only start a
>DM on :0,
>all other "heads" get the message "No Display Manager available
>for this
>Screen".
>
>Any ideas out there?
>
>-Brian Bates
>Bowater, Thunder Bay.
>
>
>
>_______________________________________________________________________
>
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
Other related posts: