At 04:28 PM 5/18/04 -0400, Jaime Claramunt R. (Inforsa) wrote:
>hey list,
>
>does anybody have a tip for this ...
>we have some flowmeters (AIN) that still indicates some when there is no
>flow...
>this is used then in ACCUM blocks, and I want to find the way to indicate
>this block to accumulate only values over a low limit...with limits ?
>clamping ? (without hold ...)
I don't understand your "without hold ..." comment, but am going to
toss out my solution anyway. Here goes....
For some reason, the SCI of 7 (low flow cut-off) doesn't work for me,
even though it's a pretty plain-jane mass meter sending 4-20mA signal
through an FBM 4. My solution: I tie the close limit switch of the
block valve going to this meter to the HOLd parameter of the ACCUM
block: valve closes, ACCUM goes into hold and stops accumulating.
(Yeah, I know, one of these days the limit switch is going to fail and
somebody will have to fiddle with the ACCUM block, but it works well for now.)
Hope this helps.
Duc
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
- References:
- [foxboro] just a tip
- From: Jaime Claramunt R. (Inforsa)
Other related posts:
- » Re: [foxboro] just a tip
- » Re: [foxboro] just a tip
- » Re: [foxboro] just a tip
- » Re: [foxboro] just a tip
- » Re: [foxboro] just a tip
- » Re: [foxboro] just a tip
- » Re: [foxboro] just a tip
- » Re: [foxboro] just a tip
- » Re: [foxboro] just a tip
- [foxboro] just a tip
- From: Jaime Claramunt R. (Inforsa)