Re: [foxboro] foxboro Digest V8 #280

In a message dated 8/25/2008 01:03:09 Central Daylight Time,  
foxboro@xxxxxxxxxxxxx writes:
Dear  All,
We have problems with FBM 214 all channels getting elevated 10 to 20 %  than
real field readings. FBM rev is 2.35F . By reinitialising the FBM gets  back
to normal readings and functions. Is any one facing similar  problems.



Please don't be offended if I mention a few things you may have  already 
checked.  This is obviously an FBM for Hart protocol devices (which  are 
inconvenient in Fox I/A anyway, requiring RIN and ROUT blocks for their  
accompanying 
AIN and AOUT blocks to have decent functionality).   Check that your MGAIN on 
the RINs are 1.0 and that your KSCALEs and BSCALEs on  your AIN blocks are, 
respectively, 1.0 and 0.  Make sure your SCIs on your  AIN blocks are 0.  
Finally, watch that filtering in the AIN  block (FLOP and FTIM) are not set too 
high.
 
RGC
12803 Josey Creek Ct.
Cypress, TX 77433
713-805-8742  cell
281-256-1111 home office/FAX
281-256-1333  home



**************It's only a deal if it's where you want to go. Find your travel 
deal here.      
(http://information.travel.aol.com/deals?ncid=aoltrv00050000000047)


 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: