Dear All,
We have problems with FBM 214 all channels getting elevated 10 to 20 % than
real field readings. FBM rev is 2.35F . By reinitialising the FBM gets back
to normal readings and functions. Is any one facing similar problems.
Please don't be offended if I mention a few things you may have already
checked. This is obviously an FBM for Hart protocol devices (which are
inconvenient in Fox I/A anyway, requiring RIN and ROUT blocks for their
accompanying
AIN and AOUT blocks to have decent functionality). Check that your MGAIN on
the RINs are 1.0 and that your KSCALEs and BSCALEs on your AIN blocks are,
respectively, 1.0 and 0. Make sure your SCIs on your AIN blocks are 0.
Finally, watch that filtering in the AIN block (FLOP and FTIM) are not set too
high.
RGC
12803 Josey Creek Ct.
Cypress, TX 77433
713-805-8742 cell
281-256-1111 home office/FAX
281-256-1333 home
**************It's only a deal if it's where you want to go. Find your travel
deal here.
(http://information.travel.aol.com/deals?ncid=aoltrv00050000000047)
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
Other related posts:
- » Re: [foxboro] foxboro Digest V8 #280