Are there more options for IOMOPT than the standard 0,1,3 ?
Yes, IOMOPT = 2 lets the block listen to whatever number or connection you
put on the MEAS parameter at the bottom. And yes, a lot can be done with
KSCALE and BIAS (standard procedure for reading J themocouples which arrive in
C
where most of us want to display in F. The funny thing I've found about
scaling, however, is that (and I may have this backwards) the alarming and
ranging are based on the output units, not the input units, so you kind of have
to
watch that.