Re: [foxboro] dump alarm states
- From: Kurt J Russell <RUSSELL_KURT_J@xxxxxxxxx>
- To: foxboro@xxxxxxxxxxxxx
- Date: Mon, 19 Jul 2004 06:41:18 -0500
Jaime,
There are "pref" commands that allow the lights on the annunciator to
be turned on, flash, or turn off.
The syntax for changing the light state is:
pref -WPLBUG dmcmd "annun panel# button# state"
where panel# is the annunciator panel# (note that the first
annunciator keyboard has panels 1-3, the second keyboard has panels 4-6,
etc)
button# is the button number (1-16) within the panel
state is the desired light state: 5=flash, 4=off,
3=on
To reset particular light:
pref -WPLBUG dmcmd "annun 1 2 4"
This would take the light on Panel 1 Button 2 and turn if OFF
I hope this helps
Kurt Russell