Re: [foxboro] display access
- From: "Schouten, Frits JF" <Frits.Schouten@xxxxxxxxxxxxxxxxxx>
- To: "'foxboro@xxxxxxxxxxxxx'" <foxboro@xxxxxxxxxxxxx>
- Date: Tue, 27 Jan 2004 11:57:44 +1100
Content-Type: text/plain
The Environment files for the WP20/30 are (if they are hosted by a 50
series) at /usr/fox/ia16/usr/fox/sys/Chang_Env
And you can't edit them with vi or any other normal editor. They are semi
binary.
You have to use the Environment Configurator on the PW20/30
If you have it handy, it's all in Workstation Configuration B0193AG Rev B.
I actually looked it up in the FoxDocx 6.5-7(K0173TQ-L)
Cheers,
Frits.
-----Original Message-----
From: William C. Ricker [mailto:wcricker@xxxxxxxxxxxxxxx]
Sent: Tuesday, 27 January 2004 13:14
To: foxboro@xxxxxxxxxxxxx
Subject: Re: [foxboro] display access
Dusting off the old books....
Sr. Gomez has an AP20, probably with WP20s or WP30s.
In that system it is a separate problem from the "SELECT"
button in the menu bar. I only wish I remembered how to
do things to the 20 series Current Alarm Display, as I suspect
he is asking about.
Sr. Gomez, You aught to mention that yours is an AP20 system
because most folks on this list will be thinking of 50 or 70
series systems.
As to the sepcific problem, if memory serves, there are different
templates stored away somewhere on the system disk which may
be used in place of the standard CAD template. One of these
may have the Detail button deleted. Also, there is somewhere
a file with equates that define how the Display Manager
operates. In the 50 series, this is "wp50_glbls.all" and is
in "/usr/fox/wp/data". A second one includes those values the
user is expected to modify; "init.user" in the same directory.
I know the name(s) and path are different in the AP20, but I dont
remember what it is. Possible somewhere under "/usr/diskless"
or "/usr/fox/hi".
Good luck
William C. Ricker
FeedForward, Inc.
Marietta, GA, USA
wcricker@xxxxxxxxxxxxxxx
770-426-4422
-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx
[mailto:foxboro-bounce@xxxxxxxxxxxxx]On Behalf Of Duc M Do
Sent: Monday, January 26, 2004 6:31 PM
To: foxboro@xxxxxxxxxxxxx
Subject: Re: [foxboro] display access
At 11:54 PM 1/26/04 +0100, oswald gomez wrote:
>hi guys, can anybody help configure my displays to not allow the
>operators to access to the "block detail" windows. I've noticed that in
>their environment, they can totally modify any control loop by pressing
>the buton "block detail". I'd like to stop this, so that changes could
>only be done under the engineering environment.
>
>Is there any file I can look at?
Isn't this the same question you posed three days ago and several
people had already taken the time to help you with possible solutions?
http://www.freelists.org/archives/foxboro/01-2004/threads.html#00159
and scroll down to thread #49.
Duc
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
EOM
NOTICE - This message and any attached files may contain information that is
confidential and/or subject of legal privilege intended only for use by the
intended recipient. If you are not the intended recipient or the person
responsible for delivering the message to the intended recipient, be advised
that you have received this message in error and that any dissemination,
copying or use of this message or attachment is strictly forbidden, as is
the disclosure of the information therein. If you have received this
message in error please notify the sender immediately and delete the
message.
-- No attachments (even text) are allowed --
-- Type: application/octet-stream
-- File: IA Series 6.5-7.0 (K0173TQ-L).lnk
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
Other related posts: