Joen, Do you have annunciator keyboards configured for both WPs? You need two files for each WP an alarm panel file, <wplnam>AAPAN, and an alarm table file, <wplnam>AATAB. The filenames must include the workstation logical name. If you only have one set for the WP where the annunciator works just copy the files and reboot the WP. Kathy Grace Systems Engineering & Development, Invensys Systems, Inc. -----Original Message----- From: joen [mailto:joen@xxxxxxxxxxxxxxxxxx] Sent: Wednesday, December 12, 2001 12:05 PM To: foxboro@xxxxxxxxxxxxx Subject: [foxboro] WP problems - persisting hallo, guys pls. help me out on the following problem: system: 2 WP (old), and 1 AP (new, Z-series), I/A Series ver 6.1.1 one of the WPs is suffering from: * annunciator keyboard being not functioning, no LED nor horn * annunciator keyboard cannot associate with displays * cannot start VT100 session reboot station is normal, with similar result cabling check OK putting the annunciator keyboard into the other WP, and functioning OK my guess is that it needs AP reboot; am i correct? thank you in advance for all suggestions cheers ___________________________________________________________________ This list is neither sponsored nor endorsed by The Foxboro Company. Use the information obtained here at your own risk. For disclaimer, see http://www.thecassandraproject.org/disclaimer.html#maillist list info: http://www.freelists.org/list/foxboro subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave ___________________________________________________________________ This list is neither sponsored nor endorsed by The Foxboro Company. Use the information obtained here at your own risk. For disclaimer, see http://www.thecassandraproject.org/disclaimer.html#maillist list info: http://www.freelists.org/list/foxboro subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave