Hi
We have a calc block that checks the quality of the Object manager
variables and outputs a Boolean if good. For stations we use
CPNAME_STA:STATION.MINUTE, for workstations we use an object manager
global variable on each workstation, (the same variable as our tags
button is linked to it is created on boot using
/opt/fox/bin/tools/omcrt). The problem with this is if the cp goes down
where we have the calc block, the graphic thinks everything has gone. I
guess you could link straight to the object manager variables. We have
done it this way as we wanted to generate an alarm as well as display on
a graphic, and we have a small system. I have not shown the statuses of
FBMs but you may be able to link into an ECB parameter. Not sure if
this is wise or if it would work though. Shaun Goldie wants to know if
anyone got a good picture of 200 series FBM in foxdraw ?
Example of calc code.
RI01 =3D MY1FCP_STA:STATION.MINUTE
BI02 =3D MYAW01_TAGS
STEP01 =3D RQL RI01
STEP02 =3D OUT BO01
STEP03 =3D RQL BI02
STEP04 =3D OUT BO02
Sean
-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx]
On Behalf Of Karthik MS
Sent: Tuesday, 25 December 2007 8:05 PM
To: foxboro@xxxxxxxxxxxxx
Subject: [foxboro] System Architecture graphics - Object manager
variables
Hi!
I intend to make a System Architecture graphics in Foxdraw to display
the
System healthiness. Where do I get the object manager variables
information,
so that I could use them in my custom graphics.
Any info/help will be highly appreciated.
Thanks!
Karthik.
=0A=0ANOTICE - This message and any attached files may contain informatio=
n that is confidential and intended only for use by the intended recipien=
t. If you are not the intended recipient or the person responsible for de=
livering the message to the intended recipient, be advised that you have =
received this message in error and that any dissemination, copying or use=
of this message or attachment is strictly forbidden, as is the disclosur=
e of the information therein. If you have received this message in error =
please notify the sender immediately and delete the message.
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
Other related posts: