Re: [foxboro] Suddenly loading the AApan file doesn't work to assign displays to the annunciator keypad

Perhaps what you are loading is not actually getting into the panel.

 There is a way to dump the memory of the annuciator panel to get the 
configuration that is actually being executed on the station. It is something 
like this:

pref -LBUG ascmd printalmpnl

(or it might be "prtalmpnl" I can't remember off hand)

This will create a file in /usr/fox/alarms with a "WPLOGICNAME.prt" (look for 
the "prt" extension)

Then have a look at the dump file to see if it matches your configuration.

Good Luck

Peter



 
 