Re: [foxboro] PI question

Mr. Lowell,


>Does anyone have a list of which types of Foxboro objects can be written to
>by PI?

Look at the Control Blocks Descriptions books.  For each block, a table
is shown listing PARAMETERS.  It has an ACCESSABILITY column, which lists
for each parameter if it can be connected to, and if it can be 'set'. Both
must be true if PI is to write to the value.


>I really wanted to use the REAL.VALUE, ...

Given what I understand from my limited PI work, I'd expect it would work.
Is there perhaps a range problem?


>CALC.M01

Right.  It won't work.  Not connectable, not settable.


Regards,

William C. Ricker
FeedForward, Inc.