Re: [foxboro] Operator action journal auto start at boot up

Has to be wp51_glbls.all ; wp51_glbls is
overwriten during station boot so no edit
to that file survives.

If the 'OLOG= ...' line is put in before the 
lines 'gctsize 14' and 'dmlist OJLOG' it will
work, but not if its after them.

Also, we try to avoid edits to wp51_glbls.all
because of conflicts at system upgrade.  It 
changes frequently from version to version, meaning
custom edits must be reapplied.  Also edits 
to this file are commonly overlooked during upgrades,
causing troubleshooting cycles, etc.  On the other
hand, 'init.user' is not overwritten at upgrade and
is more likely remembered.

W C Ricker
FeedForward, Inc.
Marietta GA



-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx
[mailto:foxboro-bounce@xxxxxxxxxxxxx]On Behalf Of Nowlan, Trevor
Sent: Friday, December 07, 2001 1:43 PM
To: 'foxboro@xxxxxxxxxxxxx'
Subject: Re: [foxboro] Operator action journal auto start at boot up



Try using the same line in 

/usr/fox/wp/data/wp51_glbls

instead of

/usr/fox/wp/data/init.user



Trevor Nowlan
Systems Integration & IT
Foxboro Canada Inc.
Montreal, Quebec, Canada
<mailto:Tnowlan@xxxxxxxxxx>
Phone: 514-421-8118
Fax: 514-421-8054


 
 
___________________________________________________________________
This list is neither sponsored nor endorsed by The Foxboro Company.
Use the information obtained here at your own risk. For disclaimer,
see http://www.thecassandraproject.org/disclaimer.html#maillist

list info:   http://www.freelists.org/list/foxboro
subscribe:   mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave

Other related posts: