Re: [foxboro] Not able to load compound

> It give the following error message.
> Compond name : SIM_UCM1
> name used ; create failed
> select continue to proceed
>=20

Hi,

it may be that the Compound is still in the CSA.

1) Do a check sync on all your AWs especially on the Host machine of the
CP which contained the SIM_UCM1

# cd /opt/fox/bin/tools/db_sync/
# ck_multi_cps

2) Check the CSA database

http://www.thecassandraproject.org/wiki/index.php/Absolutely_everything_
there_is_to_know_about_CSA

Regards,
Andreas
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: