Re: [foxboro] MDACT on ESSCOR simulator
- From: "Parker, Janet" <Janet.Parker@xxxxxxxxxxxx>
- To: foxboro@xxxxxxxxxxxxx
- Date: Wed, 14 May 2003 09:44:36 -0700
Hi Cyrus,
I believe you are not referencing the block quite right. It should resemble
that listed below.
Cross Reference as <compound>:<block>.FBLIMDEC
<compound>:<block>.FBLIMINC
Please feel free to contact me directly so that I can help you through this
problem.
Regards,
Janet Parker
Senior Applications Engineer
SimSci-Esscor
T (760) 268-7774
F (760) 268-7707
-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx
[mailto:foxboro-bounce@xxxxxxxxxxxxx]On Behalf Of Cyrus W. Taft
Sent: Wednesday, May 14, 2003 8:32 AM
To: Foxboro Mailing List
Subject: [foxboro] MDACT on ESSCOR simulator
I have a very early vintage ESSCOR power plant simulator that uses the FS=
IM
software to handle the control system model. The disk drive in the maste=
r
simulation computer crashed a few months ago and through a comedy of erro=
rs
there was no current backup. ESSCOR has managed to reconstruct the syste=
m
for me and I have worked through several bugs in getting the system worki=
ng
again. I have one last known problem with the MDACT block. There are tw=
o
drive limit switch inputs to the MDACT FBM which are linked to two
parameters, LIMINC and LIMDEC. The problem I have is that the LIMDEC
parameter is always true which prevents the MDACT block from pulsing the
drive in the decrease direction. ESSCOR uses a cross reference file to
link process model variable names to Foxboro inputs and outputs. For thes=
e
two inputs, the cross reference file links them both to logical constants=
that are always false. Obviously something is not right with the cross
referencing. ESSCOR generally uses a slightly different parameter name i=
n
the cross reference file than Foxboro. For example, to connect a model
variable to an AIN block, ESSCOR uses the parameter name .POINT instead o=
f
.PNT. But in the case of the these limit switch inputs, the parameter na=
me
is the same, LIMINC and LIMDEC. I wonder if someone else with an early
vintage ESSCOR simulator with an MDACT block could check their CrossRef.t=
xt
file and tell me what parameter name is used for these two points. =
Thanks for your help.
Cyrus Taft
EPRI I&C Center
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
- Follow-Ups:
- Re: [foxboro] MDACT on ESSCOR simulator
- From: Cyrus W. Taft
Other related posts:
- » Re: [foxboro] MDACT on ESSCOR simulator
- » Re: [foxboro] MDACT on ESSCOR simulator
- Re: [foxboro] MDACT on ESSCOR simulator
- From: Cyrus W. Taft