Tom,
 
Looks like the IPC task name has already been registered.  Try running sipc to 
see if you currently have a process registered with something like 
ICCAPI[CPNAME]
cd /opt/fox/bin/tools
sipc
list dt
 
If your CP is in the list somewhere something else has not released the IPC 
name.  I think the control configurator uses a different IPC name from my 
memory(MTBF=10 minutes), which is why you can use the control configurator.
 
If this is your problem the news is I do not know how to fix it other than a 
reboot, but it is windows!  You might be able to trace the pid of the ipc name. 
 type dt ICCAPI[CPNAME] in the sipc window and it gives you information about 
the process.  The PID might be HEX from that same dodgy memory.
 
Sean
 
________________________________

From: foxboro-bounce@xxxxxxxxxxxxx on behalf of Weiss, Andreas
Sent: Fri 21/12/2007 8:46 a.m.
To: foxboro@xxxxxxxxxxxxx
Subject: Re: [foxboro] Load MESH FCP Using iccdrvr.tsk and Print File format



Dear Tom,

the iccdrvr.tsk is working on my MESH AW70 with V8.3.

That's not really a help for you but it may motivate you to get it done.

Regards,
Andreas




-- No attachments (even text) are allowed --
-- Type: application/ms-tnef
-- File: winmail.dat


 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: