Re: [foxboro] Int30 Question

The best way to optimize Int 30 traffic is to pack the bits on the AB side  
into  integers and pass that through the gateway.  Read the integers  on the 
Foxboro side and address individual bits in the integers for the controls  and 
displays.  Remember to put all of the integers you generate in the PLC  in  
contiguous memory locations in the plc to avoid multiple reads from the  
integrator. You should be able to get a great many digitals this way with  
minimal 
load on the serial link
 
Chuck Leddon
Triconex

 
 