Re: [foxboro] Iaconnect OPC-Server
- From: "Ainuddin Ali" <ainuddin@xxxxxxxxx>
- To: foxboro@xxxxxxxxxxxxx
- Date: Fri, 21 Nov 2008 20:03:22 +0800
Hi Marcel
What's the main advantage of this OPC server over AIM*AT OPC server? does it
have support for A&E standard now?
Regards
Ainuddin Ali
Prai Power Plant
On Fri, Nov 21, 2008 at 6:29 PM, Sieling, Marcel <
Marcel.Sieling@xxxxxxxxxxxxxxxx> wrote:
> Hi list,
>
> Patrick, thanks for the flowers.
>
> You wrote about the IAConnect OPC server:
> >It directly addresses the low-level Object Manager [,,,]
>
> That's correct but it's important to understand it uses legal calls
> and no "back doors" or undocumented stuff.
>
> <advertising>
> It's just an OPC Server based on I/A series OM calls with native
> SSC support, independent of FoxAPI or AIMAPI installations and
> runs on all Windows based IA machines (NT, XP or Server 2003,
> latest OM quickfixes required). The IAConnect OPC server works
> withy dynamic OM lists and handles them properly and efficiently
> for write and read access to the IA series variables (connectable
> or non connectable).
> </advertising>
>
> If anyone is interested I'd be glad to redirect your questions, requests
> or issues to the appropriate person in our german organization.
>
> Best regards / Mit freundlichen Grüßen
>
> Marcel Sieling
> Senior Application Consultant
>
> Invensys Systems GmbH
> Emanuel-Leutze-Str. 11
> D-40547 Düsseldorf
>
> T: +49 (0)211 5966 302
> F: +49 (0)163 99 5966 302
> M: +49 (0)163 5966 302
> E: marcel.sieling@xxxxxxxxxxxxxxxx
> http://www.ips.invensys.com
>
> Geschäftsführer: Harald Konermann, Hartmut Wallraf - Amtsgericht Düsseldorf
> - HRB 37252
> Hauptsitz der Firma: Emanuel-Leutze-Str.11, 40547 Düsseldorf, Germany
>
>
>
>
> -----Original Message-----
> From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx]
> On Behalf Of foxpat
> Sent: Friday, November 21, 2008 8:03 AM
> To: foxboro@xxxxxxxxxxxxx
> Subject: Re: [foxboro] Supervisory control
>
> Andriny
>
> We use Supervisory Setpoint Sontrol with the IAconnect OPC server (Invensys
> Germany software). The IAconnect OPC is specifically designed to handle the
> SSC mechanism and does this without any problems (1 applic, for 1 year,
> zero
> problems). It directly addresses the low-level Object Manager and therefore
> does not require AIM* and performance is FAST!
>
> Using AIM*OPC is possible but is much more complex to setup. We decided not
> to go that route as we've heard IAconnect was very simple to implement.
> (which proved to be absolutly true).
>
> The standard FoxDoc includes the SSC documentation which describes the SSC
> mechanism (don't have access to that here, so don't know the exact doc.
> Number).
> The IAconnect manual describes how to implement the IAconnect.
> I had this running on a AW70 integrator V7.1 for test and used some
> home-made visual basic programs to read/write IA blocks, including SSC
> (PIDA).
>
> Highly recommended!
>
>
> Kind regards,
> Patrick Martens
> Total Raff. Ned. NV.
>
>
>
> -----Oorspronkelijk bericht-----
> Van: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx]
> Namens Andriny Bt Rusman (R&T/PETH)
> Verzonden: vrijdag 21 november 2008 4:38
> Aan: foxboro@xxxxxxxxxxxxx
> Onderwerp: [foxboro] Supervisory control
>
> All,
>
> I have a question on the Supervisory Control. I'm using Foxboro v7.1.1 &
> wants to implement advanced controls which will require an external
> controller to write to the existing PIDE controllers. I know you can
> set the SUPOPT = 1 and this enables writing SPT from external (in this
> case, via OPC), but I heard this way is fraught with problems.
>
> Can someone confirm this?
>
> Best regards,
> Andriny Rusman
> Advanced Process Control Engineer,
> PETRONAS
> email: andriny@xxxxxxxxxxxxxxx
>
>
>
>
>
> * Confidentiality Notice:
> This e-mail and any associated files are intended solely for the individual
> or entity to whom they are addressed. Please do not copy it or use it for
> any purposes, or disclose its contents to any other person. Further, this
> e-mail and any associated files may be confidential and further may be
> legally privileged. This email is from the Invensys Process Systems business
> unit of Invensys plc which is a company registered in England and Wales with
> its registered office at Portland House, Bressenden Place, London, SW1E 5BF
> (Registered number 166023). For a list of European legal entities within
> the Invensys Process Systems business group, please click here
> http://www.invensys.com/legal/default.asp?top_nav_idw&nav_id&prev_idw
> .
>
> If you have received this e-mail in error, you are on notice of its status.
> Please notify us immediately by reply e-mail and then delete this message
> from your system. Thank you for your co-operation. You may contact our
> Helpdesk on +44 (0)20 7821 3859 / 2105 or email
> inet.hqhelpdesk@xxxxxxxxxxxxx This e-mail and any attachments thereto may
> be subject to the terms of any agreements between Invensys (and/or its
> subsidiaries and affiliates) and the recipient (and/or its subsidiaries and
> affiliates).
>
>
>
>
> _______________________________________________________________________
> This mailing list is neither sponsored nor endorsed by Invensys Process
> Systems (formerly The Foxboro Company). Use the info you obtain here at
> your own risks. Read http://www.thecassandraproject.org/disclaimer.html
>
> foxboro mailing list: http://www.freelists.org/list/foxboro
> to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
> to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
>
>
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html