Re: [foxboro] ICC to CP disconnect

Hi Barry,

How's Kinleith?

I like your suggestion better than mine.  I never thought of moving
the AW over to the testbed.  Much better than my method of using an
offline AW and then copying files.

Cheers,

Kevin

On 2/20/08, Cassie, Barry (Kinleith) <Barry.Cassie@xxxxxxxxx> wrote:
> Scary stuff happens -
> You could take the AW with the icc problems down to your spare system,
> attach a CP with letterbug of the problem CP then initialize and reboot
> it.
> Hopefully you have a good & recent saveall that you can then load.
> AW can then be returned to the plant and then checkpoint the CP.
> The only problems now will be any block/compound mismatches that have
> occurred after the date of your saveall. D/U should be ok to fix this.
> This should be better than initialise CP attached to the plant.
> Barry
>
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 