Re: [foxboro] ICC help
- From: duc.do@xxxxxxxxxxxxxx
- To: foxboro@xxxxxxxxxxxxx
- Date: Thu, 16 Dec 2004 14:22:45 -0500
And also this thread in Nov 2003:
http://www.freelists.org/archives/foxboro/11-2003/msg00088.html
This Alex Johnson fellow is really a fount of knowledge, I tell ya....
In all likelihood your CSA database is okay, so it's just a matter of fixing
your workfile. When I ran into this kind of problems in the past (yes,
several times), I'd do a SaveAll, load that SaveAll into an off-line CP, and
then copy the workfile for that CP (in /opt/fox/ciocfg/<CPlbug>) from the
off-line system to the on-line system, with all precautions taken, of
course!
As Alex says somewhere in his voluminous notes, it's not for the faint of
heart. But then, in my case, the official route of
"Initialize/Reboot/LoadAll" is not an option, so you get brave real quick.
Good luck, Troy!
Duc
--
Duc M. Do
Dow Corning Corp.
Carrollton Plant
Carrollton, KY, US
-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx
[mailto:foxboro-bounce@xxxxxxxxxxxxx]On Behalf Of pedersen.em@xxxxxx
Sent: Thursday, December 16, 2004 1:45 PM
To: foxboro@xxxxxxxxxxxxx
Subject: Re: [foxboro] ICC help
Check Alex Johnsons write-up from 4/11/2003 on the freelists.org archive
for this group. Search for CP sync and it along with a lot more should
pop up. I have only gone the official route of performing a load-all
because I have the luxury of periodic shutdowns. Good Luck.
Eric M. Pedersen
Procter & Gamble Paper Products Company
C&IS Engineering
Troy L Brazell <tlbrazell@xxxxxxxxxxxxxxx>
Sent by: foxboro-bounce@xxxxxxxxxxxxx
12/16/2004 09:59 AM
Please respond to foxboro
To: foxboro@xxxxxxxxxxxxx
cc: (bcc: Eric Pedersen-EM/PGI)
Subject: [foxboro] ICC help
Okay, after many years of working with IA my worst nightmare came true. The
AW shutdown with the ICC open. Several (quite a few) new blocks had been
built. When the machine rebooted and I opened the ICC the new blocks were
gone. They are still in the CP because they are working and linked to the
graphic. How can I resync the ICC database with the work file? Or what is
the recovery from this?
Thanks
Troy
Troy L. Brazell
Duke Energy Field Services
Sr. Process Control Analyst
ISA CCST
Phone (405) 263 4810 ext. 24
Cell (806) 898 4340
Okarche C&M
Route 4 P.O. Box 40
Okarche, OK. 73762
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
Other related posts: