Re: [foxboro] How can i use 'Clear Page' for all Alarm-Managers
- From: "Johnson, Alex (Foxboro)" <ajohnson@xxxxxxxxxxx>
- To: foxboro@xxxxxxxxxxxxx
- Date: Mon, 24 May 2004 10:24:00 -0400
The Common Alarm Group does what you want.
Make sure you have CLR_OPT set to 1 or 2 in your init.user file.
Regards,
Alex Johnson
Invensys Systems, Inc.
10707 Haddington
Houston, TX 77043
713.722.2859 (voice)
713.722.2700 (operator)
713.932.0222 (fax)
ajohnson@xxxxxxxxxxx
For the latest information on ArchestrA, go to
http://www.invensys.com/Archestra.html.
-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On
Behalf Of Hegewisch, Dirk
Sent: Monday, May 24, 2004 7:40 AM
To: Foxboro Newsgroup (E-Mail)
Subject: [foxboro] How can i use 'Clear Page' for all Alarm-Managers
Hi List,
what is the way to configure a redundant alarm manager configuration?
I need the functionality that using the "Clear page" AM-button on one =
AW51C has at the same time the same result on a second AW51C.
What I've already done?
1) Configuring an error free /usr/fox/alarms/*AApan-file
2) Configuring an error free /usr/fox/alarms/*AAtab-file using a =
selfmade script
(my script checks the existence of display files configured in the =
*AApan-file and supresses double entries of Compound:Blocks in the =
*AAtab-file)
3) Configuring an Alarm Manager config-file using AMDC
I avoided the usage of an config-file for every AW/WP. Here a snippet of =
the /usr/fox/alarms/Q7332U/am.log file.
12:10:54 5-3-04 Trying /usr/fox/customer/alarms/cfg/Q7332U.cfg.
12:10:54 5-3-04 Unable to open config file =
/usr/fox/customer/alarms/cfg/Q7332U.cfg
12:10:54 5-3-04 Trying /usr/fox/customer/alarms/cfg/am_def.cfg.
Configuring a *cfg-file for every AW/WP does not solve my problem.
Another point of interest is that I had an running system on V6.1 where =
the functionality had exists. Now at V6.5 and V6.51 is the functionality =
not given or not right configured.
Q7332U# more commgrp.cfg
#
# Common Alarm Group (CAG) Configuration File
#
# (CAD Redirection)
# WP CAG Backup BLK TOP USER CAG
# LBUG NAME1 LBUG DTL PRIO DISP NAME2
Q7331U CAGNAME Q7332U ------ ------ ------ ------------
Q7332U CAGNAME Q7331U ------ ------ ------ ------------
Q7331U#
A solution could be a script that sends an amcmd to the second AW-AM but =
is there no standard foxboro solution built-in?
Regards
Dirk
BP Cologne
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
Other related posts: