Re: [foxboro] How can i use 'Clear Page' for all Alarm-Managers
- From: "Boulay, Russ" <Russ.Boulay@xxxxxxxxxxxx>
- To: "'foxboro@xxxxxxxxxxxxx'" <foxboro@xxxxxxxxxxxxx>
- Date: Mon, 24 May 2004 08:55:36 -0400
The file /usr/fox/wp/data/init.user
parameter CLR_OPT=1 (means delete the alarm from all alarm displays in
the Common Alarm Group)
> -----Original Message-----
> From: foxboro-bounce@xxxxxxxxxxxxx On Behalf Of "Hegewisch,
> Dirk" <Dirk.Hegewisch@xxxxxxxxx>
> Sent: Monday, May 24, 2004 8:40 AM
> To: Foxboro Newsgroup (E-Mail)
> Subject: [foxboro] How can i use 'Clear Page' for all Alarm-Managers
>
> Hi List,
>
> what is the way to configure a redundant alarm manager configuration?
>
> I need the functionality that using the "Clear page" AM-button on one =
> AW51C has at the same time the same result on a second AW51C.
>
> What I've already done?
>
> 1) Configuring an error free /usr/fox/alarms/*AApan-file
>
> 2) Configuring an error free /usr/fox/alarms/*AAtab-file using a =
> selfmade script
> (my script checks the existence of display files configured in the =
> *AApan-file and supresses double entries of Compound:Blocks in the =
> *AAtab-file)
>
> 3) Configuring an Alarm Manager config-file using AMDC
>
> I avoided the usage of an config-file for every AW/WP. Here a snippet of =
> the /usr/fox/alarms/Q7332U/am.log file.
>
> 12:10:54 5-3-04 Trying /usr/fox/customer/alarms/cfg/Q7332U.cfg.
> 12:10:54 5-3-04 Unable to open config file =
> /usr/fox/customer/alarms/cfg/Q7332U.cfg
> 12:10:54 5-3-04 Trying /usr/fox/customer/alarms/cfg/am_def.cfg.
>
> Configuring a *cfg-file for every AW/WP does not solve my problem.
>
> Another point of interest is that I had an running system on V6.1 where =
> the functionality had exists. Now at V6.5 and V6.51 is the functionality =
> not given or not right configured.
>
> Q7332U# more commgrp.cfg
> #
> # Common Alarm Group (CAG) Configuration File
> #
> # (CAD Redirection)
> # WP CAG Backup BLK TOP USER CAG
> # LBUG NAME1 LBUG DTL PRIO DISP NAME2
> Q7331U CAGNAME Q7332U ------ ------ ------ ------------
> Q7332U CAGNAME Q7331U ------ ------ ------ ------------
> Q7331U#
>
>
> A solution could be a script that sends an amcmd to the second AW-AM but =
> is there no standard foxboro solution built-in?
>
> Regards
> Dirk
>
> BP Cologne
>
>
> _______________________________________________________________________
> This mailing list is neither sponsored nor endorsed by Invensys Process
> Systems (formerly The Foxboro Company). Use the info you obtain here at
> your own risks. Read http://www.thecassandraproject.org/disclaimer.html
>
> foxboro mailing list: http://www.freelists.org/list/foxboro
> to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
> to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
>
-- No attachments (even text) are allowed --
-- Type: application/ms-tnef
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
Other related posts: