Re: [foxboro] How can i use 'Clear Page' for all Alarm-Managers

The file /usr/fox/wp/data/init.user
parameter  CLR_OPT=1   (means delete the alarm from all alarm displays in
the Common Alarm Group)

>  -----Original Message-----
> From:         foxboro-bounce@xxxxxxxxxxxxx   On Behalf Of "Hegewisch,
> Dirk" <Dirk.Hegewisch@xxxxxxxxx>
> Sent: Monday, May 24, 2004 8:40 AM
> To:   Foxboro Newsgroup (E-Mail)
> Subject:      [foxboro] How can i use 'Clear Page' for all Alarm-Managers
> 
> Hi List,
> 
> what is the way to configure a redundant alarm manager configuration?
> 
> I need the functionality that using the "Clear page" AM-button on one =
> AW51C has at the same time the same result on a second AW51C.
> 
> What I've already done?
> 
> 1) Configuring an error free /usr/fox/alarms/*AApan-file
> 
> 2) Configuring an error free /usr/fox/alarms/*AAtab-file using a =
> selfmade script
> (my script checks the existence of display files configured in the =
> *AApan-file and supresses double entries of Compound:Blocks in the =
> *AAtab-file)
> 
> 3) Configuring an Alarm Manager config-file using AMDC
> 
> I avoided the usage of an config-file for every AW/WP. Here a snippet of =
> the /usr/fox/alarms/Q7332U/am.log file.
> 
> 12:10:54 5-3-04 Trying /usr/fox/customer/alarms/cfg/Q7332U.cfg.
> 12:10:54 5-3-04 Unable to open config file =
> /usr/fox/customer/alarms/cfg/Q7332U.cfg
> 12:10:54 5-3-04 Trying /usr/fox/customer/alarms/cfg/am_def.cfg.
> 
> Configuring a *cfg-file for every AW/WP does not solve my problem.
> 
> Another point of interest is that I had an running system on V6.1 where =
> the functionality had exists. Now at V6.5 and V6.51 is the functionality =
> not given or not right configured.
> 
> Q7332U# more commgrp.cfg
> #
> #         Common Alarm Group (CAG) Configuration File
> #
> #                                (CAD Redirection)
> #  WP      CAG      Backup       BLK    TOP   USER          CAG
> # LBUG    NAME1      LBUG        DTL    PRIO  DISP         NAME2
> Q7331U CAGNAME      Q7332U      ------ ------ ------    ------------
> Q7332U CAGNAME      Q7331U      ------ ------ ------    ------------
> Q7331U#
> 
> 
> A solution could be a script that sends an amcmd to the second AW-AM but =
> is there no standard foxboro solution built-in?
> 
> Regards
> Dirk
> 
> BP Cologne
> 
> 
> _______________________________________________________________________
> This mailing list is neither sponsored nor endorsed by Invensys Process
> Systems (formerly The Foxboro Company). Use the info you obtain here at
> your own risks. Read http://www.thecassandraproject.org/disclaimer.html
> 
> foxboro mailing list:             http://www.freelists.org/list/foxboro
> to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
> to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
>  


-- No attachments (even text) are allowed --
-- Type: application/ms-tnef


 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: