Re: [foxboro] Hiding Clear Alarms button in CAD
- From: brad.s.wilson@xxxxxxxxxxxxxx
- To: foxboro@xxxxxxxxxxxxx
- Date: Tue, 23 Aug 2005 11:38:16 -0400
I'm in the middle of doing this right now ... removing the Clear & Block
Detail buttons.
20-series CAD ... the templates are in usr/fox/tmplts or
usr/fox/ia16/usr/fox/tmplts and can be modified with the Display
Builder/Configurator
50-series CAD ... use the DispAlarmCfg tool ... the procedure is quite
involved and is detailed in B0193RV, section 9
The AM must be restarted for the changes to take place using ...
pref -AMNAME amcmd "quitam on ; exit"
where AMNAME is the name of your alarm manager.
Rather than releting the buttons, consider changing their permission level
to Engineer.
Don't just do the CAD ... there are other alarm displays which can have
Clear & Block Detail button ... MRA, NEWALM, ACKED, UNACK, AHD
Good luck,
Brad Wilson
ExxonMobil Chemical Co
Edison Synthetics Plant
732-321-6115
732-321-6177 fax
Brad.S.Wilson@xxxxxxxxxxxxxx
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
- References:
- [foxboro] Hiding Clear Alarms button in CAD
- From: Baptiste, Nigel
Other related posts:
- » Re: [foxboro] Hiding Clear Alarms button in CAD
- » Re: [foxboro] Hiding Clear Alarms button in CAD
- [foxboro] Hiding Clear Alarms button in CAD
- From: Baptiste, Nigel