Re: [foxboro] Gateway Initialization
- From: "Joe Gale (MP)" <JGALE@xxxxxxxxxxx>
- To: "'foxboro@xxxxxxxxxxxxx'" <foxboro@xxxxxxxxxxxxx>
- Date: Tue, 23 Apr 2002 12:30:19 -0500
I don't have a written procedure for this, but I had to do this same thing
with a CP40 due to a missing compound.
First thing I did was to get a printout of the missing compound/blocks using
dbvu. Its located in /opt/fox/bin/tools , I think I used the -t option to
get a parameter report.
Next would be doing a saveall, initialize, reboot, loadall. Then you can
use the printout to rebuild the compound and blocks that are missing. Good
luck.
Joe Gale
DCS Administrator
Boswell Energy Center
Minnesota Power
1210 NW 3rd Street
Cohasset, MN 55721
218-328-5036 Ext. 4611
email: jgale@xxxxxxxxxxx
-----Original Message-----
From: Jriccardi@xxxxxxx [mailto:Jriccardi@xxxxxxx]
Sent: Tuesday, April 23, 2002 11:59 AM
To: foxboro@xxxxxxxxxxxxx
Subject: [foxboro] Gateway Initialization
Folks,
I would appreciate any help in identifying the specific IA document that
describes the CP/Gateway initialization procedure (assume they are the same
procedure). I have an A-B Gateway with a Compound that appears in the
Select
Display listing, but does not appear in the ICC. Cannot explain how it
happened (can only guess), but from memory, there is an initialization
procedure that must be followed that will resolve (something like ...,
SaveAll, Initialize CP/Gateway, reinstall ECB's, Load Compounds, rebuild
missing Compound, etc.). I do not want to overlook a critical step, so
would
like to follow a documented procedure.
I have tried the CSC search utility, and manually searched a number of IA
documents, all with no success in finding documentation on the
Initialization
procedure.
Thanks for any help/advice you can provide ...
Joe Riccardi
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
Other related posts: