Re: [foxboro] FoxCAE Loadall problem

Regarding transfer from fox CAE if you have a windows station with control 
you can load your database file to ICC then use ICC DRIVER TASK to change to 
a text file transfer it to unix edit it and load it back ok here is how
on windows station
/opt/fox/ciocfg/api/
sh
iccdrvr.tsk -d <fname>
OPEN CPNAME ALL ROOT
GET *:* ALL
CLOSE
EXIT
Now you should have a filename with name you have choosen then copy it to a 
diskette and open it on the unix station.
edit this file
right at the top of it
OPEN <CPNAME> ALL ROOT
change ever NAME= to ADD through find and replace.
add at the end of file
CLOSE
EXIT
then go to
/opt/fox/ciocfg/api/
iccdrvr.tsk -i fname
this should create a load all on your CP provided no compounds have the same 
name or blocks are not supported by this CP. hope this works try it on your 
own risk best of luck

Tarek


 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: