Re: [foxboro] FV and DM Xterminal Displays from same AW51
- From: "Deen, Ron" <rdeen@xxxxxxxxxxx>
- To: "'foxboro@xxxxxxxxxxxxx'" <foxboro@xxxxxxxxxxxxx>
- Date: Thu, 10 Apr 2003 09:20:07 -0400
There is one other thing:
Running the go_dm script for Xterminals will by default give you the
"default_dm"
When you want to be able to have a choice you may have to make some
modifications to this file:
Find the line that reads"/opt/fox/wp/bin/default_dm"and change that to:
For the default leave as is
For Foxview: /opt/fox/wp/foxview/foxview
For DM: /usr/fox/wp/bin/dm_wp50
Name the two script go_FV and go_DM for instance and run the script when you
log in
This is what I do in our lab
Good luck
Ron Deen
-----Original Message-----
From: mvurda@xxxxxxx [mailto:mvurda@xxxxxxx]
Sent: donderdag 10 april 2003 14:48
To: foxboro@xxxxxxxxxxxxx
Subject: [foxboro] FV and DM Xterminal Displays from same AW51
We have a AW51D running V6.3 with both DM and FV installed. Currently, there
are three X-terminals connected and displaying DM graphics, which is the
current default graphics environment on the AW51.
A new line is being installed, and we want to us FV graphics for this line,
and display them on another X-terminal connected to the same AW51. Current
X-terminals are using Exceeed 7.
Does anyone have experience with a similar setup? Any suggestions or
comments would be greatly appreciated.
Mark V. Urda
Synergy Systems Inc.
528 West 5th Avenue
Naperville, IL 60563
phone: 630-778-1960
fax: 630-778-7926
cell: 630-248-9382
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
Other related posts: