Re: [foxboro] FDSI gateway differences again
- From: "Wilson, Brad" <brad.wilson@xxxxxxxxxxxxxxxx>
- To: <foxboro@xxxxxxxxxxxxx>
- Date: Wed, 22 Oct 2008 10:25:54 -0400
Why wouldn't you build one DCI block and connect other blocks to that?
Read FDSI --> DCI --> as many input blocks as you like
Write FDSI <-- DCI <-- CALC or SWCH <-- multiple output blocks
Brad Wilson
brad.wilson@xxxxxxxxxxxxxxxx
Invensys Process Systems, Inc
1090 King Georges Post Rd, Suite 204
Edison, NJ 08837
732-661-4012 o
732-874-0087 c
-----Original Message-----
Does anyone know a way to get the FDSI to allow two blocks to read
and/or write to the same point through the FDSI. It was possible to do
this on the gateways/integrators. There are instances where this
behavior is useful, and was used in an integrator we are modifying. The
only way to duplicate the previous functionality will involve getting GE
to re-write their Modbus interface. (Which might be a little pricier
than our Gateway conversion.) If anyone has a secret way to allow this
"error" to be replicated in the FDSIs, let me know.
Thanks,
David
* Confidentiality Notice:
This e-mail and any associated files are intended solely for the individual or
entity to whom they are addressed. Please do not copy it or use it for any
purposes, or disclose its contents to any other person. Further, this e-mail
and any associated files may be confidential and further may be legally
privileged. This email is from the Invensys Process Systems business unit of
Invensys plc which is a company registered in England and Wales with its
registered office at Portland House, Bressenden Place, London, SW1E 5BF
(Registered number 166023). For a list of European legal entities within the
Invensys Process Systems business group, please click here
http://www.invensys.com/legal/default.asp?top_nav_id=77&nav_id=80&prev_id=77.
If you have received this e-mail in error, you are on notice of its status.
Please notify us immediately by reply e-mail and then delete this message from
your system. Thank you for your co-operation. You may contact our Helpdesk on
+44 (0)20 7821 3859 / 2105 or email inet.hqhelpdesk@xxxxxxxxxxxxx This e-mail
and any attachments thereto may be subject to the terms of any agreements
between Invensys (and/or its subsidiaries and affiliates) and the recipient
(and/or its subsidiaries and affiliates).
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
- References:
- [foxboro] FDSI gateway differences again
- From: David Johnson
- Re: [foxboro] FDSI gateway differences again
- From: Ken Heywood
Other related posts:
- » Re: [foxboro] FDSI gateway differences again
- » Re: [foxboro] FDSI gateway differences again
- » Re: [foxboro] FDSI gateway differences again
- » Re: [foxboro] FDSI gateway differences again
- » Re: [foxboro] FDSI gateway differences again
- [foxboro] FDSI gateway differences again
- From: David Johnson
- Re: [foxboro] FDSI gateway differences again
- From: Ken Heywood