I am sure we have set the IOMOPT = 1 IOM_ID SCI=3/SCO=3 etc. correctly. Thanks for your precious time and reply. 于 2012-1-18 16:29, Dirk Pauwels 写道: > > Q1: If your FBM is online and on scan it should be ok I guess > Q2: not that I know off, we have plenty of them and can't remember we had > problems during install > Q3: Did you enter the IOM_ID and point nr? > IOMOPT = 1? > Did you enter the SCI=3/SCO=3? > > Rgds, > Dirk > > -----Original Message----- > From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On > Behalf Of Jason.LJZ > Sent: Wednesday, January 18, 2012 11:28 AM > To: foxboro@xxxxxxxxxxxxx > Subject: [foxboro] FBM204 failed to be recognized by system > > Dear all, > > I just ran into a problem: we need to add a FBM204 to our system, which is > I/A 7.0 with 4 pairs CP60 and six AW51/WP51(Sun Blade 150) stations. > > Before we added the FBM204, the system has no other FBM204 installed. We > added a ECB2 and configured it as HWTYPE=204, SWTYPE=2. AIN and AOUT were > added and configured. > > The status of ECB2 was ONLINE and ON_SCAN. > > The problem is when we checked the AIN and AOUT block, the AIN block was > indicated as BAD I/O even the transmitter outside worked normally. When we > set output of AOUT as 50%, no milliampere can be measured. > > We also added a FBM241C to our system, and it works fine once it was added. > The difference is there are FBM241C already used in system. > > My question is: > > 1. Does it matter that there are same type FBM already installed in system? > So the newly added modules can be recognized by system? > > 2. Is there any thing special about adding FBM204 to system? > > 3. What can I do to probably solve the problem? > > Thanks in advance for your precious time for reading this and any help is > appreciated. > > > _______________________________________________________________________ > This mailing list is neither sponsored nor endorsed by Invensys Process > Systems (formerly The Foxboro Company). Use the info you obtain here at your > own risks. Read http://www.thecassandraproject.org/disclaimer.html > > foxboro mailing list: //www.freelists.org/list/foxboro > to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join > to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave > > > > _______________________________________________________________________ > This mailing list is neither sponsored nor endorsed by Invensys Process > Systems (formerly The Foxboro Company). Use the info you obtain here at > your own risks. Read http://www.thecassandraproject.org/disclaimer.html > > foxboro mailing list: //www.freelists.org/list/foxboro > to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join > to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave > _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave