Re: [foxboro] FBM 233 to Controllogix question

David
On ModbusTCP we thought we could use a 233 pair connected to a PLC with
1 Ethernet port by using the IPaddress/node notation the master and
backup have the same IPaddress but different node numbers, this would
initially work but then smurff a while later not sure what made it
smurff but I thought it was related to using ICC on the DCI blocks.
For modbusTCP IP addresses have to be unique across the FBM pair
Shaun




NOTICE - This message and any attached files may contain information that is 
confidential, legally privileged or proprietary.  It is intended only for use 
by the intended recipient. If you are not the intended recipient or the person 
responsible for delivering the message to the intended recipient, be advised 
that you have received this message in error. Any dissemination, copying, use 
or re-transmission of this message or attachment, or the disclosure of any 
information therein, is strictly forbidden. BlueScope Steel Limited does not 
represent or guarantee that this message or attachment is free of errors, virus 
or interference. 
   
If you have received this message in error please notify the sender immediately 
and delete the message.  Any views expressed in this email are not necessarily 
the views of BlueScope Steel Limited.
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: