David,
Are you packing the information in the Controllogix into data files and then
reading the data files via Ethernet communications?
If you do not pack the data and read contiguous bytes, the overhead load
becomes very high, even with ethernet speeds. I had experience a few years ago
where AW70 ethernet was reading/writing Contollogix and this same type of
failure would occur from time to time. Since the writes are change driven, too
many writes (not periodic) with your basic reads would lock up the
communication.
Terry
Objet : [foxboro] FBM 233 to Controllogix question
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
- References:
- [foxboro] FBM 233 to Controllogix question
- From: David Johnson
Other related posts:
- » Re: [foxboro] FBM 233 to Controllogix question
- » Re: [foxboro] FBM 233 to Controllogix question
- » Re: [foxboro] FBM 233 to Controllogix question
- » Re: [foxboro] FBM 233 to Controllogix question
- » Re: [foxboro] FBM 233 to Controllogix question
- » Re: [foxboro] FBM 233 to Controllogix question
- » Re: [foxboro] FBM 233 to Controllogix question - mike kessler
- » Re: [foxboro] FBM 233 to Controllogix question - Jack.Easley
- » Re: [foxboro] FBM 233 to Controllogix question - Doucet, Terrence
- » Re: [foxboro] FBM 233 to Controllogix question - mike kessler
- » Re: [foxboro] FBM 233 to Controllogix question - David Johnson
- » Re: [foxboro] FBM 233 to Controllogix question - Olsson, Scott
- [foxboro] FBM 233 to Controllogix question
- From: David Johnson