Re: [foxboro] FBM 215
- From: Corey R Clingo <corey.clingo@xxxxxxxx>
- To: foxboro@xxxxxxxxxxxxx
- Date: Wed, 12 Jul 2006 11:59:00 -0400
You also cannot hit it directly with an AOUT. You must build an ROUT, and
then if you need more than the paltry functionality an ROUT provides,
build an AOUT that feeds it.
Corey Clingo
BASF Corporation
Kevin FitzGerrell <fitzgerrell@xxxxxxxxxxxxxxx>
Sent by: foxboro-bounce@xxxxxxxxxxxxx
07/11/2006 07:24 PM
Please respond to
foxboro@xxxxxxxxxxxxx
To
"foxboro@xxxxxxxxxxxxx" <foxboro@xxxxxxxxxxxxx>
cc
Subject
Re: [foxboro] FBM 215
Terry,
You should be good with ECB 200 HWTYPE 215 SWTYPE 215.
You also need ECB201 for each field device - do you have those configured
yet?
ECB 201 HWTYPE 215 SWTYPE 215 PARENT - pathname of ECB200
Regards,
Kevin FitzGerrell
Carter Holt Harvey, Ltd.
+64 27 460 9994
Quoting Terry Currie <TCurrie@xxxxxxxxxx>:
> How do I configure a FBM 215?
> Used ECB 200 HWTYPE 215 SWTYPE 215
> I tried using a aout and it shows invaild hwtype / swtype
> Terry
>
>
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
- References:
- Re: [foxboro] FBM 215
- From: Kevin FitzGerrell
Other related posts:
- » Re: [foxboro] FBM 215
- » Re: [foxboro] FBM 215
- » Re: [foxboro] FBM 215
- » Re: [foxboro] FBM 215
- Re: [foxboro] FBM 215
- From: Kevin FitzGerrell