- From: Corey R Clingo <corey.clingo@xxxxxxxx>
- To: foxboro@xxxxxxxxxxxxx
- Date: Wed, 12 Jul 2006 12:39:22 -0500
I don't think you can invert the high and low scales, but you can play
with KSCALE and BSCALE (e.g., -1.0 and 100 to get a 100 to 0 reading) to
invert the reading.
Most of these transmitters have the option of current output inversion as
well.
Corey Clingo
BASF Corporation
"Moore, Kenneth, Celanese/US" <ken.e.moore@xxxxxxxxxxxx>
Sent by: foxboro-bounce@xxxxxxxxxxxxx
07/12/2006 07:03 AM
Please respond to
foxboro@xxxxxxxxxxxxx
To
<foxboro@xxxxxxxxxxxxx>
cc
Subject
[foxboro] Easy AIN question
I have an application coming up where I would like to use a guided
radar level transmitter to measure the amount of free space remaining in
a vessel. Being somewhat of an I/A novice, I thought I'd ask the experts
before proceeding.=20
The guides will be 72" long. If I enter the scaling in reverse order, 72
as low and 0 as high, will the indication be inverted? 4mA=3D72 and
20mA=3D0? Thus the read out on the display will be the amount of =
uncovered
guide.
Regards,
Ken Moore
Process Controls Specialist
Celanese=20
Enoree, SC 29335
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
- References:
- [foxboro] Easy AIN question
- From: Moore, Kenneth, Celanese/US
Other related posts:
- » Re: [foxboro] Easy AIN question
- » Re: [foxboro] Easy AIN question
- » Re: [foxboro] Easy AIN question
- [foxboro] Easy AIN question
- From: Moore, Kenneth, Celanese/US