Re: [foxboro] Display Manager Stops Running on WP51F on Ver. 7.1.1
- From: Jim Kahlden <Jim.Kahlden@xxxxxxxx>
- To: "foxboro@xxxxxxxxxxxxx" <foxboro@xxxxxxxxxxxxx>
- Date: Tue, 29 Jul 2008 09:25:52 -0500
Thanks to those sending suggestions to my problem with a display manager as
shown below. Seems that I had 2 problems. First was a hard drive that was
marginal as I was getting lost+found errors in the /var/adm/messages file from
the /opt partition. Replaced the drive and that cleared that problem. Issue
with the DM going away was related to a display the operators would call up
from the Current Alarm Display (CAD). Whenever they called up a block detail
from the CAD the displayed block detail would blink at different rates. I
copied over the /opt/fox/dd_1/DFLT directory from a working station to this
station and the problems have cleared.
Jim
-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On
Behalf Of Jim Kahlden
Sent: Monday, July 21, 2008 8:49 AM
To: foxboro@xxxxxxxxxxxxx
Subject: [foxboro] Display Manager Stops Running on WP51F on Ver. 7.1.1
Has anyone experienced the display manager to stop working on a running WP5=
1F box running version 7.1.1 software? Last week and again today I have ha=
d an experience where the display manager was not running on the box. This=
is a dual headed box and is run in the Windows Off mode. What I have seen=
is one head completely dark and the other has the Current Alarm page runni=
ng. Normally I could select the Previous Display button on the CAD and it =
would take me to the FoxView display that was running, but that does not wo=
rk. I can log in remotely to the box and when doing the ps -eaf command, t=
here are no DM processes running. There are no messages in the /var/adm/me=
ssage file indicating any type of failure. To get the box working again I =
just do a shutdown remotely and the restart the box and it works again. An=
y suggestions where to look first?
Thanks,
Jim Kahlden
System Reliability Analyst
Lower Colorado River Authority
Fayette Power Project
6549 Power Plant Road
La Grange, TX 78945
(979) 249-8514 (Ph)
(979) 249-8390 (Fax)
jim.kahlden@xxxxxxxx
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
- References:
- Re: [foxboro] Running Hours Counter
- From: Ghamdi, Bander M
- [foxboro] Display Manager Stops Running on WP51F on Ver. 7.1.1
- From: Jim Kahlden
Other related posts:
- » Re: [foxboro] Display Manager Stops Running on WP51F on Ver. 7.1.1
- » Re: [foxboro] Display Manager Stops Running on WP51F on Ver. 7.1.1
- » Re: [foxboro] Display Manager Stops Running on WP51F on Ver. 7.1.1
- Re: [foxboro] Running Hours Counter
- From: Ghamdi, Bander M
- [foxboro] Display Manager Stops Running on WP51F on Ver. 7.1.1
- From: Jim Kahlden