Shaun,

For the peer-to-peer connection to work, you'll need to first Checkpoint the
CP.  Does that correct your problem?

Regards,

Doug Lloyd
DGL Controls

-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx]On
Behalf Of ShaunBenetti@xxxxxxxxxxxxx
Sent: Friday, July 11, 2003 12:03 PM
To: foxboro@xxxxxxxxxxxxx
Subject: [foxboro] Configurator Help

I am using IA ver=2E 4=2E3 and am having some trouble=2E  I am trying to
send an analog output to a point located in a different compound and
CP than where the input and other logic resides=2E  I normally do not
do this but don't have a choice this time=2E  When I configure the
block It does not see the measurement=2E  Is there anyway I can do
this?  Thanks for any help=2E

Regards,

Shaun =20



_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html

foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave


 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: