    If I understand what you are saying, there is normally no problem
passing values across the nodebus/Lan, using standard Cmpd:Block.Parameter
addressing in the sink block.  One small possibility I can think of is that
a peer-to-peer connection (i.e. CP to CP) is not established until a
Checkpoint is completed.  So you would not see the measurement on the sink
block until after the checkpoint.

Rich Bakke
Longview Fibre Co.

ShaunBenetti@xxxxxxxxxxxxx wrote:

> I am using IA ver=2E 4=2E3 and am having some trouble=2E  I am trying to
> send an analog output to a point located in a different compound and
> CP than where the input and other logic resides=2E  I normally do not
> do this but don't have a choice this time=2E  When I configure the
> block It does not see the measurement=2E  Is there anyway I can do
> this?  Thanks for any help=2E
>
> Regards,
>
> Shaun =20
>
>
>
> _______________________________________________________________________
> This mailing list is neither sponsored nor endorsed by Invensys Process
> Systems (formerly The Foxboro Company). Use the info you obtain here at
> your own risks. Read http://www.thecassandraproject.org/disclaimer.html
>
> foxboro mailing list:             http://www.freelists.org/list/foxboro
> to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
> to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
>

 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: