Re: [foxboro] CSA X 2
- From: "Johnson, Alex (Foxboro)" <ajohnson@xxxxxxxxxxx>
- To: foxboro@xxxxxxxxxxxxx
- Date: Wed, 16 Feb 2005 19:06:34 -0500
I would like to add that you may not have identical CSA databases. You will
need to use the 'LAN Merge' utilities to examine the CSA databases and
reconcile them.
If not, bad things may happen when you are building blocks later.
You can get instructions and help from your friendly Field Service
representative.
Regards,
Alex Johnson
Invensys Process Systems
Invensys Systems, Inc.
10707 Haddington
Houston, TX 77043
713.722.2859 (voice)
713.722.2700 (switchboard)
713.932.0222 (fax)
ajohnson@xxxxxxxxxxx
-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On
Behalf Of John Metsker
Sent: Wednesday, February 16, 2005 10:46 AM
To: foxboro@xxxxxxxxxxxxx
Subject: Re: [foxboro] CSA X 2
Rob,
CSA is started through the /usr/fox/bin/fox_apps.dat mechanism.
Removing the ACSA entry in this file will prevent CSA from starting on a
machine.
The /usr/fox/csa/CSA_SERVER process is CSA. A kill -9 would be the
right way to stop it. However, the start-up also sets a global variable
on the system. You may have to reboot the AP(W) where it wasn't
supposed to run to allow it to run on another machine.
John Metsker
General Mills, Inc. =20
-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx]
On Behalf Of Burnham, Rob C.
Sent: Wednesday, February 16, 2005 9:27 AM
To: Foxboro free list (E-mail)
Subject: [foxboro] CSA X 2
List,
Have two CSA's running!
Can someone remind me of the file to edit to stop CSA from starting,
and what should I kill to stop it?
TIA
Rob Burnham
Systems Engineer
Glatfelter
<http://www.glatfelter.com>
Phone 920-727-2426
Fax 920-727-2638
rburnham@xxxxxxxxxxxxxx
=20
=20
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
=20
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: =
mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin
to unsubscribe: =
mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave
=20
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
Other related posts: