Re: [foxboro] CP270 Partner gone

Andreas,

Is that an FBM231 or 233 on your CP270?  There is a "partner gone"
error code for those.

From the error code manual:
Partner gone (231 and 233 only). The FBM's redundant partner has
stopped responding. This can be caused by the physical removal of the
partner, by a "reset" of the partner, or by a failure of the partner.

Regards,

Kevin FitzGerrell

On 8/21/08, Weiss, Andreas <Andreas.Weiss@xxxxxxxxx> wrote:
> Hi List,
>
> what does the following message mean?
>
> 21-08-08 05:36:46   *  0  SYSMON = SM2000  Q17B0C  Process = Q1720Cb0801
>           -39  10701 115321:Partner Gone.
>
> 10-08-08 04:58:04 * 0 SYSMON = SM2000 Q71B0C Process = Q71B0Am0723
>             -39 10701 173557:Partner Gone.
>
>
> Regards,
> Andreas
>
>
> _______________________________________________________________________
> This mailing list is neither sponsored nor endorsed by Invensys Process
> Systems (formerly The Foxboro Company). Use the info you obtain here at
> your own risks. Read http://www.thecassandraproject.org/disclaimer.html
>
> foxboro mailing list:             http://www.freelists.org/list/foxboro
> to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
> to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
>
>
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 