Re: [foxboro] COUT out of GRXDVX

Yes, most definitely. The file you need to edit is /usr/fox/alarms/horn.cfg
and the instructions are in horn_cfg.man. Reboot the AW/WP to load the new
horn.cfg into the Alarm&Alert subsystem. (You have to toggle an IFL which,
in turn, activates your COUT in a simple ladder rung.)

Duc

-- 
Duc M. Do
Dow Corning Corp.
Carrollton Plant
Carrollton, KY, US

-----Original Message-----
From: RAYMUNDO MENDEZ [mailto:mendezrw@xxxxxxxxx]
Sent: Friday, October 25, 2002 11:32 AM
To: foxboro@xxxxxxxxxxxxx
Subject: [foxboro] COUT out of GRXDVX


I would like to set a COUT to trigger a horn conected to FBMs located 1=
mile away from control room whenever I have an alarm from blocks inside=
that compound, Is this possible?.

Regards

Raymundo M=E9ndez
=