Re: [foxboro] Best Alarm Package for Ver 8 MESH

We have PlantStateSuite from PAS here, and I find that the situation is 
just the opposite.  The PAS principals come from a Honeywell background, 
and PAS software reflects that by trying to make everything look like 
Honeywell.  While much of the philosophy between TDC and I/A is common, 
some is not, and the terminology is different; this has already caused 
some confusion with people doing alarm management activities here. Another 
issue is that PSS does not understand the concept of alarm destinations, 
so you might have data showing up in your alarm reports than never emits a 
peep at an operator console.  I had to write some custom scripts here to 
collect and filter the alarm data before sending it to the PAS alarm 
server to get around that.

That said, we are getting some value out of it (as we probably would with 
any alarm management tool).  The UI in the client looks nice, but is 
surprisingly unintuitive for infrequent users; however, we mostly work 
from canned reports anyway.  The I/A collection interface actually works 
better than the TDC one (!), so I personally can't complain too much 
there.  We do have an issue on our one v8 system where operator action 
messages get garbled, but we've determined that that is a problem with the 
AIM*ODBC driver, which PSS uses for collection on that system.  It's not 
my plant so I don't know if they ever resolved it.


I have never used Matrikon alarm management, so I don't know about them. 
But TiPS' package looked functional if not necessarily pretty, and they've 
been doing I/A for a long time.  Also, PSS is definitely a "full blown 
alarm management package" that is quite complex.


Corey Clingo
BASF Corporation






"Jenckes, Jim R." <JJenckes@xxxxxxxxxxx> 
Sent by: foxboro-bounce@xxxxxxxxxxxxx
01/30/2009 10:44 AM
Please respond to
foxboro@xxxxxxxxxxxxx


To
<foxboro@xxxxxxxxxxxxx>
cc

Subject
Re: [foxboro] Best Alarm Package for Ver 8 MESH






We are presently using Matrikon, but have heard the of another company
that may be better integrated into the I/A world. 
You might want to check these folks out PAS. Check out this link
http://news.thomasnet.com/fullstory/478442 for some info. There also is
a website www.pas.com, but I had trouble getting to it. 

Jim Jenckes, CCST
Process Controls Specialist
Tesoro Alaska Co.
907-776-3865

-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx]
On Behalf Of Jack.Easley@xxxxxxxxxxxx
Sent: Saturday, January 24, 2009 9:56 AM
To: foxboro@xxxxxxxxxxxxx
Cc: Clifford.Adams@xxxxxxxxxxxx
Subject: [foxboro] Best Alarm Package for Ver 8 MESH

Group,
 

I am looking for recommendations for the best 3rd party package to deal
with alarm and alarm message extraction from the AIM Historian. I know
Tips has been around a long time, but have heard yeas and nays about it.
I've also heard FoxRay is pretty good. Ideally, I'd like to hear from
someone with experience with several of these options to determine the
best.

 

The only thing we are looking for is a simple Windows AIM alarm/alarm
message extraction application that is easy to search and create simple
reports on an infrequent basis. We don't really need a full blown alarm
management package that is overly complicated.

 

Thanks in advance,

Jack Easley
Sr. I&C Technician
Luminant Power, Martin Lake Plant
Phone 903.836.6241
jack.easley@xxxxxxxxxxxx 

 





 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: