Jeff,
I hate to ask a dumb question, but I'd rather do that than to make a dumb 
mistake.  Are you sure about the block arrangement you presented?  

In the situation you describe, the BIAS block needs a BCALCI from the AOUT, but 
there is only the one BCALCO in the AOUT.  That is good, so leave it there. 
(You should also connect AOUT.INITO to the BIAS.INITI.)

The SWCH block can take a BCALCI but, since the AIN does not need a BCALCI 
there is no need to connect any BCALC to the SWCH block.  Then, it will not be 
TRACKING.  

Now, if the SWCH block was between the BIAS block and the AOUT, then you would 
use the BCALC connections to pass data through the SWCH from the AOUT to the 
BIAS.

Or, I could be wrong.  

Chuck Jones
Automation Technologist
Tate & Lyle South Plant
office 765.477.5324 
cell 765.586.5290


-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On 
Behalf Of Jeff Hurt
Sent: Tuesday, July 14, 2009 9:33 AM
To: foxboro@xxxxxxxxxxxxx
Subject: [foxboro] BCALCI/BCALCO question

We're building a control loop that looks like this:
 
AIN -> SWITCH BLOCK -> BIAS BLOCK -> AOUT
 
The connections are made automatically in the IACC.  When the BCALCI, BCALCO, 
BCALC1, BCALC2 connections are made, there is no output out of the switch block 
and it indicates it is tracking.  When the BCALC connections are removed, 
everything works correctly and the switch block no longer indicates 
it is tracking.  Any thoughts as to why it doesn't work with the BCALC 
connections?
 
Thanks,
Jeff  
 
 


********************************************************************************************************
This email and any files transmitted with it are confidential and intended 
solely for the 
use of the individual or entity to whom they are addressed. If you are not the 
intended 
recipient or the person responsible for delivering the email to the intended 
recipient, be 
advised that you have received this email in error that any use, dissemination, 
forwarding, printing, or copying of this email is strictly prohibited.  If you 
have received 
this email in error please notify the sender immediately. Please note that we 
reserve 
the right to monitor and read any emails sent and received by the Company in 
accordance with and to the extent permitted by applicable legal rules.

Tate & Lyle PLC, registered in England: number 76535. Registered office: Tate & 
Lyle PLC, Sugar Quay,
Lower Thames Street, London EC3R 6DQ. 

Tate & Lyle Industries Limited registered in England:number 699090.
Registered office: Tate & Lyle Industries Limited, Sugar Quay, Lower Thames 
Street,
London EC3R 6DQ
*********************************************************************************************************

 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: