Re: [foxboro] Architecture problem


Steve,
Sorry if I misunderstand you but are you saying you can use an AW51 to do
the same thing as you do with Exceed on a pc? Can you pull up displays from
another node from an AW? You wrote "log in as user "ia" where do you do
this? from a vt session? This sounds very interesting. Please let me know
if this is what you ment or if I misunderstand.

Thanks!



                                                                                
                                       
                    "Murray, Steve"                                             
                                       
                    <SMurray@xxxxxxxxx       To:     "'foxboro@xxxxxxxxxxxxx'" 
<foxboro@xxxxxxxxxxxxx>                 
                    m>                       cc:                                
                                       
                    Sent by:                 Subject:     Re: [foxboro] 
Architecture problem                           
                    foxboro-bounce@fre                                          
                                       
                    elists.org                                                  
                                       
                                                                                
                                       
                                                                                
                                       
                    02/20/2002 10:19                                            
                                       
                    AM                                                          
                                       
                    Please respond to                                           
                                       
                    foxboro                                                     
                                       
                                                                                
                                       
                                                                                
                                       






Hi Damien,

  We have two separate I/A systems that are only connected through their
second Ethernet cards and our corporate LAN.

  Mostly we "look" at the other side using our PCs and Exceed, but we can
just as easily connect using our AW51's.  Just log in as user "ia" and the
login script provides the display.  It might not be a good idea to use the
ICC remotely very often if you can avoid it.

  We have even logged our AW51's in to I/A systems in other states across
our corporate WAN, and a PC using Exceed  for Old Display Manager or Go
Global for FoxView works pretty good across a telephone line.

  Steve Murray
  Asarco



-----Original Message-----
From: Damien AMPE [mailto:d.ampe@xxxxxxxxxxxxx]
Sent: Wednesday, February 20, 2002 8:52 AM
To: 'foxboro@xxxxxxxxxxxxx'
Subject: [foxboro] Architecture problem



Hi list,

I have a "little" architecture problem and perhaps someone of you has the
solution.

We have to connect an I/A Series node (V6.11) to another site where we want
to install a new node. These two nodes are in different town. We have a
specialised line (private phone line) to connect the two site.

In the first site, we have AW51E, AW51B and AW51D on a LAN (V6.11).

In the second one, we would like to install an AW70 or AW51D to communicate
with an Siemens PLC (S7-400).

My problem is : How to connect the two AWxx for having the same functions
on
the two. (Same display, same ICC config if we have to dialog with the PLC
from the two site)
And on the new site, if the communication is lost, the local node will
continue to work.

I hope you understand my question.

Thanks

<><><><><><><><<><><><><><><><<><><><><><><><>

This e-mail and any files transmitted with it are the property of Americas
Mining Corporation and/or its affiliates, are confidential, and are
intended solely for the use of
the individual or entity to whom this e-mail is addressed. If you are not a
named recipient or otherwise have reason to believe that you have received
this message in error,
please notify the sender and delete this message immediately from your
computer. Any other use, retention, dissemination forwarding, printing or
copying of this e-mail is
strictly prohibited.  Although this email and any attachments are believed
to be free of any virus or other defect that might affect any computer
system into which it is
received, and opened, it is the responsibility of the recipient to ensure
that it is virus free and no responsibility is accepted by Americas Mining
Corporation and/or its
affiliates for any loss or damage arising in any way from its use

This e-mail has been scanned and cleared by MailMarshal
www.marshalsoftware.com

<><><><><><><><<><><><><><><><<><><><><><><><>


_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html

foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave




 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: