Re: [foxboro] Annunciator Keyboard LEDs

The ACK_HORN global was last stated in the 4.3/6.1 Release Notes
Enhancements and Problems Resolved section  4.5.29

4.5.29 Alarm Alert 
CAR#8402 IALOG#8298 Synopsis: 
The Alarm Alert subsystem allows the user to configure whether or not the
horn is 
silenced when an annunciator key is pressed. If the global ACK_HORN = N is 
defined in the /usr/fox/wp/bin/data/init.user file, when an operator presses
an annun- 
ciator key when the horn is sounding, the horn is not silenced. If the
global is not 
defined, pressing an annunciator key continues to silence the horn.



>  -----Original Message-----
> From:         foxboro-bounce@xxxxxxxxxxxxx   On Behalf Of "Corey R Clingo"
> <clingoc@xxxxxxxxxxxxx>
> Sent: Monday, January 19, 2004 1:10 PM
> To:   foxboro@xxxxxxxxxxxxx
> Subject:      Re: [foxboro] Annunciator Keyboard LEDs
> 
> 
> So, are you the only Foxboro person that knew about this?  I know this has
> come up on the list 2 or 3 times in the last couple of years, and the
> answer was always, "sorry, can't do that."
> 
> What other gems are you hiding?  :)
> 
> Corey Clingo
> BASF Corp.
> 
> 
> 
> |---------+---------------------------->
> |         |           "Grace, Kathy"   |
> |         |           <kgrace@xxxxxxxxx|
> |         |           om>              |
> |         |           Sent by:         |
> |         |           foxboro-bounce@fr|
> |         |           eelists.org      |
> |         |                            |
> |         |                            |
> |         |           01/19/2004 10:28 |
> |         |           AM               |
> |         |           Please respond to|
> |         |           foxboro          |
> |         |                            |
> |---------+---------------------------->
>  
> >-------------------------------------------------------------------------
> -----------------------------------------------------|
>   |
> |
>   |              To:  "'foxboro@xxxxxxxxxxxxx'"
> |
>   |              cc:
> |
>   |       Subject:  Re: [foxboro] Annunciator Keyboard LEDs
> |
>  
> >-------------------------------------------------------------------------
> -----------------------------------------------------|
> 
> 
> 
> 
> Hi All,
> 
> CAR 8402 was submitted to report this problem. Originally this was
> provided
> as a custom fix but was later merged into the standard workstation alarm
> management software. This was done back in July 1996. Yes you have been
> able
> to do this for 7 1/2 years.
> 
> The remaining problem and the source of confusion is that although the
> changes to support this were added to the code, the changes were never
> documented in either wp51_glbls files or in init.user.rel. I will ensure
> that the changes are made to these files going forward.
> 
> In the meantime here is what you need to do.
> 
> 1. Edit init.user (copy from init.user.rel if init.user does not exist).
> 2. Add the following to the end of the file:
> 
>  ACK_HORN=N
> 
> By default if ACK_HORN is not defined or defined as "Y" horns will be
> silence by pressing any annunciator key. Setting this to "N" will only
> silence the horns when the horn silence button ("ACK") is pressed on the
> annunciator keyboard.
> 
> One further note for those of you using FoxPanels. This only works with
> annunciator keyboards and does not work with FoxPanels.
> 
> I hope this has cleared up the confusion.
> 
> Regards,
> Kathy
> 
> 
> 
> 
> 
> 
> 
> _______________________________________________________________________
> This mailing list is neither sponsored nor endorsed by Invensys Process
> Systems (formerly The Foxboro Company). Use the info you obtain here at
> your own risks. Read http://www.thecassandraproject.org/disclaimer.html
> 
> foxboro mailing list:             http://www.freelists.org/list/foxboro
> to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
> to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
>  


-- No attachments (even text) are allowed --
-- Type: application/ms-tnef


 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: