Re: [foxboro] Alarms priorities

Thanks Brad
Does this mean that I need to do the following command to get
priorities:

getpars -U* -C* -B* -mCMPNM:%12s -mPRTYPE:%6s -mCRIT:%8x

Please confirm

Regards

Hafedh

-----Original Message-----

From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx
<mailto:foxboro-bounce@xxxxxxxxxxxxx> ] On Behalf Of
brad.s.wilson@xxxxxxxxxxxxxx

Sent: 21 October 2005 13:36

To: foxboro@xxxxxxxxxxxxx

Subject: Re: [foxboro] Alarms priorities

Hafedh Ghodhbani writes:

I used the following command to get alarms information:

getpars -U* -C* -B* -mCMPNM:%12s -mTYPE:%6s -mALMOPT:%8x

This doesn't give the alarms priorities.

Do you know how to get the alarms priorities using get= part

The terminology is confusing.

ALMOPT will tell you what type of alarm is configured CRIT will tell you
the priority (1 to 5, 0 means no alarms) PRTYPE will tell you the what
type of alarm has the highest priority (1 to 9, 0 means no alarms)

If you are proficient with working with bit-mapped packed long integer
values, there is a wealth of information that can be found in ALMSTA It
took me a while to figure it out (with help from list members), but I
now understand is well and have automated reports that extract alarm
statuses, priorities, acknowledge statuses, etc from ALMSTA.

Brad Wilson

ExxonMobil Chemical Co

Edison Synthetics Plant

732-321-6115

732-321-6177 fax

Brad.S.Wilson@xxxxxxxxxxxxxx

_______________________________________________________________________

This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
<http://www.thecassandraproject.org/disclaimer.html> 

foxboro mailing list: http://www.freelists.org/list/foxboro
<http://www.freelists.org/list/foxboro> 

to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
<mailto:foxboro-request@xxxxxxxxxxxxx?subject=join> 

to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
<mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave> 


______________________________________________________________________
BG Energy Holdings Limited
Registered in England & Wales No: 3763515
Registered address:
100 Thames Valley Park Drive
Reading, Berkshire RG6 1PT  UK
Telephone: +44 (0)118 935 3222
Website: http://www.BG-Group.com

This e-mail is intended only for the addressee named above.  As this 
e-mail may contain confidential or privileged information, please 
advise us immediately if you are not the named addressee or the person 
responsible for delivering the message to the named addressee.  The 
contents should not be disclosed to any other person nor copies taken.
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: