Re: [foxboro] A mesh question

The ZCP270 support the use of FCMs on the Mesh network.

The Mesh network's redundancy depends on multiple connections between
switches.

In your case something like this might make sense:


C ---> Switch ---------- ... ------------   -> Switch -------> A
P       |   |                                     |            W
2       |   |                                     |            7
7-------> Switch ---------- ... -------------> Switch -------> 0
0       |  |
        |  |
        FCM -----> FBMs

You could go diagonally between the switches in the buildings, but that is
too hard to draw.

I didn't show the redundant FCMs and CPs either for the same reason.


If you retain your CPs, it would resemble:


C ---> Nodebus A ----- A ---> Switch ------- ... ----- Switch --- A
P                      T        |                        |        W
6 ---> Nodebus B ----- S ---> Switch ------- ... ----- Switch --- 7
0                                                                 0
|
|
+ FCM <---> FBMs
|
|
+ FCM <---> FBMs


The ATS can be redundant too, but it's too hard to draw and I think you
understand that part.


Does this help?



Regards,
 
Alex Johnson
Invensys Systems, Inc.
10707 Haddington
Houston, TX 77063
+1 713 722 2859 (voice)
+1 713 932 0222 (fax)
+1 713 722 2700 (switchboard)
alex.johnson@xxxxxxxxxxxxxxxx
 

-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On
Behalf Of stan
Sent: Thursday, November 17, 2005 8:59 AM
To: Foxboro List
Subject: [foxboro] A mesh question

Given an existing V6 architecture that spans 2 buildings like this:

Building "A" contains the AW, and the CP's
Building "B" contains 2 WP's most of the FBM's a Comm10, and the AB
integrates.

Presently we have fiber between the buildings for nodebus extender, and
filedbus.

I'm thinking that when we upgrade to mes, I should put switches in both
buildings. 
Given that I will have at least 4 fiber pairs between the buildings, is
there some way
I can "cross connect" the switch pairs in the 2 buildings to increase my
redundancy.
Assuming of course that the CP -> FBM communications moves to the nodebus.

-- 
U.S. Encouraged by Vietnam Vote - Officials Cite 83% Turnout Despite
Vietcong Terror 
- New York Times 9/3/1967
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at