I am sorry but I don't recognize the IOMOPT options that you specif=
ied below (3D1, 3D0, etc.) maybe the list server is doing something weird d=
o to the font that you are using?
Are there more options for IOMOPT than the standard 0,1,3 ?
Thanks
Peter
-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On=
Behalf Of Johnson, Alex P (IPS)
Sent: Tuesday, April 29, 2008 3:58 PM
To: foxboro@xxxxxxxxxxxxx
Subject: Re: [foxboro] 1-5ma input on a FBM201
Peter,
It seems to me that you could do it with two AINs. I think there are two ap=
proaches that would work, but I can't try them. As they said in my old math=
texts, the proof is left to the student. :)
Option 1 - Scaled counts
Create two AINs. The first has IOMOPT=3D3D1 and is used to read your physic=
al input. Use the scaling factors on the block to change the raw counts so =
that whatever you get at 5ma is scaled to 64,000.
Connect that block's output to the MEAS of the second AIN (IOMOPT=3D3D0). I=
think it will behave as you desire.
Option 2
Create two AINs. The first has IOMOPT=3D3D1 and is used to read your physic=
al input and scale 0-5ma as you want it in engineering units.
The second AIN would have IOMOPT=3D3D2 and take in that measurement. If you=
set the scales properly, I think the OSV/BAD will kick in.
Of course, free advice is worth what you pay for it. :)
Regards,
=3D
Alex Johnson
Invensys Process Systems
10900 Equity Drive
Houston, TX 77041
713 329 8472 (voice)
713 329 1600 (switchboard)
713 329 1700 (fax)
alex.johnson@xxxxxxxxxxxxxxxx
=3D
-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx]
On Behalf Of Bruley, Peter T
Sent: Tuesday, April 29, 2008 3:44 PM
To: Foxboro@Freelists. Org (foxboro@xxxxxxxxxxxxx)
Subject: [foxboro] 1-5ma input on a FBM201
Gentlemen:
I am trying to use a FBM201 to measure 1-5ma input.
I am using an AIN & can scale the output to read 0-100% for 1-5ma i=
n however I don't get the OOS/BAD i/o bits set when I go over/under the OSV
The AIN block doesn't have a SCI for: Linear 3200 to 1600 ( 1 to 5=
mA)
Is there any way to set the raw counts scale in the AIN block manua=
lly?
Thank You,
Peter Bruley
Plant Process Computer Analyst
Xcel Energy - Sherco Generating Plant
13999 Industrial Boulevard
Becker, MN, 55308
(763) 261-3821
Peter.T.Bruley@xxxxxxxxxxxxxx
=3D
=3D
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process Sys=
tems (formerly The Foxboro Company). Use the info you obtain here at your o=
wn risks. Read http://www.thecassandraproject.org/disclaimer.html
=3D
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=3D3Djoin
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=3D3Dleave
=3D
* Confidentiality Notice:
This e-mail and any associated files are intended solely for the individual=
=3D or entity to whom they are addressed. Please do not copy it or use it =
for =3D any purposes, or disclose its contents to any other person. Further=
, this e=3D -mail and any associated files may be confidential and further =
may be legal=3D ly privileged. This email is from the Invensys Process Syst=
ems business uni=3D t of Invensys plc which is a company registered in Engl=
and and Wales with i=3D ts registered office at Portland House, Bressenden =
Place, London, SW1E 5BF =3D (Registered number 166023). For a list of Euro=
pean legal entities within t=3D he Invensys Process Systems business group,=
please click here http://www.in=3D vensys.com/legal/default.asp?top_nav_id=
=3D3D77&nav_id=3D3D80&prev_id=3D3D77.
If you have received this e-mail in error, you are on notice of its status.=
=3D Please notify us immediately by reply e-mail and then delete this mess=
age =3D from your system. Thank you for your co-operation. You may contact =
our Help=3D desk on +44 (0)20 7821 3859 / 2105 or email inet.hqhelpdesk@inv=
ensys.com. T=3D his e-mail and any attachments thereto may be subject to th=
e terms of any a=3D greements between Invensys (and/or its subsidiaries and=
affiliates) and the=3D recipient (and/or its subsidiaries and affiliates)=
.
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process Sys=
tems (formerly The Foxboro Company). Use the info you obtain here at your o=
wn risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
- Follow-Ups:
- Re: [foxboro] 1-5ma input on a FBM201
- From: Johnson, Alex P \(IPS\)
- References:
- [foxboro] 1-5ma input on a FBM201
- From: Bruley, Peter T
- Re: [foxboro] 1-5ma input on a FBM201
- From: Johnson, Alex P \(IPS\)
Other related posts:
- » Re: [foxboro] 1-5ma input on a FBM201
- » Re: [foxboro] 1-5ma input on a FBM201
- » Re: [foxboro] 1-5ma input on a FBM201
- » Re: [foxboro] 1-5ma input on a FBM201
- » Re: [foxboro] 1-5ma input on a FBM201
- Re: [foxboro] 1-5ma input on a FBM201
- From: Johnson, Alex P \(IPS\)
- [foxboro] 1-5ma input on a FBM201
- From: Bruley, Peter T
- Re: [foxboro] 1-5ma input on a FBM201
- From: Johnson, Alex P \(IPS\)