Peter,
It seems to me that you could do it with two AINs. I think there are two
approaches that would work, but I can't try them. As they said in my old
math texts, the proof is left to the student. :)
Option 1 - Scaled counts
Create two AINs. The first has IOMOPT=3D1 and is used to read your
physical input. Use the scaling factors on the block to change the raw
counts so that whatever you get at 5ma is scaled to 64,000.
Connect that block's output to the MEAS of the second AIN (IOMOPT=3D0). I
think it will behave as you desire.
Option 2
Create two AINs. The first has IOMOPT=3D1 and is used to read your
physical input and scale 0-5ma as you want it in engineering units.
The second AIN would have IOMOPT=3D2 and take in that measurement. If you
set the scales properly, I think the OSV/BAD will kick in.
Of course, free advice is worth what you pay for it. :)
Regards,
=
Alex Johnson
Invensys Process Systems
10900 Equity Drive
Houston, TX 77041
713 329 8472 (voice)
713 329 1600 (switchboard)
713 329 1700 (fax)
alex.johnson@xxxxxxxxxxxxxxxx
=
-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx]
On Behalf Of Bruley, Peter T
Sent: Tuesday, April 29, 2008 3:44 PM
To: Foxboro@Freelists. Org (foxboro@xxxxxxxxxxxxx)
Subject: [foxboro] 1-5ma input on a FBM201
Gentlemen:
I am trying to use a FBM201 to measure 1-5ma input.
I am using an AIN & can scale the output to read 0-100% for
1-5ma in however I don't get the OOS/BAD i/o bits set when I go
over/under the OSV
The AIN block doesn't have a SCI for: Linear 3200 to 1600 ( 1
to 5 mA)
Is there any way to set the raw counts scale in the AIN block
manually?
Thank You,
Peter Bruley
Plant Process Computer Analyst
Xcel Energy - Sherco Generating Plant
13999 Industrial Boulevard
Becker, MN, 55308
(763) 261-3821
Peter.T.Bruley@xxxxxxxxxxxxxx
=
=
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
=
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave
=
* Confidentiality Notice:
This e-mail and any associated files are intended solely for the individual=
or entity to whom they are addressed. Please do not copy it or use it for =
any purposes, or disclose its contents to any other person. Further, this e=
-mail and any associated files may be confidential and further may be legal=
ly privileged. This email is from the Invensys Process Systems business uni=
t of Invensys plc which is a company registered in England and Wales with i=
ts registered office at Portland House, Bressenden Place, London, SW1E 5BF =
(Registered number 166023). For a list of European legal entities within t=
he Invensys Process Systems business group, please click here http://www.in=
vensys.com/legal/default.asp?top_nav_id=3D77&nav_id=3D80&prev_id=3D77.
If you have received this e-mail in error, you are on notice of its status.=
Please notify us immediately by reply e-mail and then delete this message =
from your system. Thank you for your co-operation. You may contact our Help=
desk on +44 (0)20 7821 3859 / 2105 or email inet.hqhelpdesk@xxxxxxxxxxxxx T=
his e-mail and any attachments thereto may be subject to the terms of any a=
greements between Invensys (and/or its subsidiaries and affiliates) and the=
recipient (and/or its subsidiaries and affiliates).
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
- Follow-Ups:
- Re: [foxboro] 1-5ma input on a FBM201
- From: Bruley, Peter T
- References:
- [foxboro] 1-5ma input on a FBM201
- From: Bruley, Peter T
Other related posts:
- » Re: [foxboro] 1-5ma input on a FBM201
- » Re: [foxboro] 1-5ma input on a FBM201
- » Re: [foxboro] 1-5ma input on a FBM201
- » Re: [foxboro] 1-5ma input on a FBM201
- » Re: [foxboro] 1-5ma input on a FBM201
- Re: [foxboro] 1-5ma input on a FBM201
- From: Bruley, Peter T
- [foxboro] 1-5ma input on a FBM201
- From: Bruley, Peter T