[foxboro] ZCP-FBM connection options

All,

 

With the FCP270, the documented options to interface with FBM100s/200s
appear to be the following:


[AW]<-->[Mesh Control 
Network]<-->[FCP270]<-->[FBI-100]<-->[FBM-100]<-->[Process]
&
[AW]<-->[Mesh Control Network ]<-->[FCP270]<-->[FBM-200]<-->[Process]

 

The primary benefit of the above approaches, in my mind, is that the
interface between the FCPs and the FBMs is closed, proprietary,
point-to-point & unmanaged.

 

With the ZCP, however, the documented interfaces between the CP and the FBMs 
always
appear to be through some type of  Mesh network (either a combined Mesh
Control+Fieldbus network, or standalone Mesh Fieldbus Network).


The drawback, in my mind, is that there are TCP/IP based managed "open" network 
devices between the Controller and I/O. The impact of planned/unplanned outages 
of this mesh-control/fieldbus-network when using conventional 4-20A based 
field-devices (as opposed to FF) is essentially loss of Level 1 control. 

 

Is there a supported option to connect a ZCP to
FBM 200/100s without using the mesh-network (as possible with the FCPs)?

 

Thanks,
Daniel

 

_________________________________________________________________
Windows Live? Hotmail®: Search, add, and share the web?s latest sports videos. 
Check it out.
http://www.windowslive.com/Online/Hotmail/Campaign/QuickAdd?ocid=TXT_TAGLM_WL_QA_HM_sports_videos_072009&cat=sports
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: