[foxboro] Strange phenomenon while uploading the CP60's

I was uploading the CP60's before taking SaveAll on floppies when suddenly a 
strange thing happened.
 
There were four AOUT blocks getting input connections from the PID control 
blocks. The output blocks froze. When I went to ICC and had look at the MEAS 
parameter, instead of connection from the PID block outputs, it was showing 
numeric value which was the value that was frozen on the AOUT blocks.
 
I corrected this and made the connections in three AOUT blocks and the control 
came back.
 
Why could such a thing happen. Site people told that ths happened 3 months back 
after similar maintenance was done on Foxboro.
 
2nd point is that three AOUT blocks were in the same CP as the PID control 
block. They are normal. There is one other AOUTR block in different CP. There 
when I corrected the connections and gave it as <compd:Block.Parameter>, it is 
showing it in smurf colour. I can omget the PID block ouput but the other CP 
cannot read it. I believe that peer-to-peer connections are allowed in ICC.
 
Can anyone tells what can be the cause.
 
Regards,
 
Kashif Ijaz
INTECH Process Automation
_________________________________________________________________
Express yourself instantly with MSN Messenger! Download today it's FREE!
http://messenger.msn.click-url.com/go/onm00200471ave/direct/01/
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: