[foxboro] Save_all question
- From: "Chaiket, Thom" <tchaiket@xxxxxxxx>
- To: <foxboro@xxxxxxxxxxxxx>
- Date: Fri, 12 Dec 2008 12:13:52 -0500
The save_all script works GREAT. I will be utilizing it after I fix
this one problem.
The script fails to create a save_all for one CP (THCP01). I have
attached the save_all log.
The log suggests that there was a problem checkpointing the CP (class
=1, error= -4, text = icChkptStn: c_worevent failure). After that
failure was detected, the CP locked up and became unavailable during the
save_all step.
From the time stamp, it looks like the checkpoint error occurred about
10 minutes after upload completion. That is too coincidental with the
default TIMEOUT setting (10). I'm thinking that the parameter setting
needs to be increased.
I'm going to give this a try after lunch, but just wanted to know:
1. Is TIMEOUT used for anything else?
2. Has anyone encountered this problem? If so, what was the solution?
Thanks,
t
-----Original Message-----
From: SCADA System
Sent: Friday, December 12, 2008 11:43 am
To: Chaiket, Thom
Subject: Emailing: save_all.log
The message is ready to be sent with the following file or link
attachments:
save_all.log
Note: To protect against computer viruses, e-mail programs may prevent
sending or receiving certain types of file attachments. Check your
e-mail security settings to determine how attachments are handled.
<<save_all.log>>
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
foxboro mailing list: http://www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
Other related posts:
- » [foxboro] Save_all question - Chaiket, Thom