[foxboro] PLB First Out Logic

I have listed below an example of doing First Out logic in a PLB block.
It can have up to 29 triggers (I have only shown 3 for brevity). I am not
sure how this will format, but if there is interest I can put it on the wik=
i.
I have also done first out logic with calc blocks which can have up to
64 triggers, but the calc blocks execute slower than the PLB.

NAME =09   =09=09U200:CON200:FIRST_OUT:LADDER
DATE =09   =09=0904/27/2005
TYPE =09   =09=09PLB
DESCRP =09   =09FIRST OUT LOGIC
PERIOD =09   =091
IOM_ID =09   =09D10205
IFL_1 =09   =09VENTURI:TE_1601B.HAIND
IFL_2 =09   =09VENTURI:TE_1600A.HAIND
IFL_3 =09   =092_1COND_G:2AT_9109A.BO01
IFL_31 =09   =09:LADDER.PAKIFL.AHFFFF
IFL_32 =09   =09:LADDER.PAKIFL.AFFF8
MA =09   =09=09:LADDER.MA.1






LADDER LOGIC DIAGRAM

  =20

                                                                       =20
     IFL_1    OFL_32                                                OFL_1 =
=20
1  ---| |------|\|---------------------------------------------------(L)---
              LATCH                                                       =
=20
                                                                          =
=20
  =20

                                                                       =20
     IFL_2    OFL_32                                                OFL_2 =
=20
2  ---| |------|\|---------------------------------------------------(L)---
              LATCH                                                       =
=20
                                                                          =
=20
  =20

                                                                       =20
     IFL_3    OFL_32                                                OFL_3 =
=20
3  ---| |------|\|---------------------------------------------------(L)---
              LATCH                                                       =
=20


                                                                       =20
     OFL_1                                                          OFL_32=
=20
30 ---| |---+--------------------------------------------------------(L)---
            |                                                       LATCH =
=20
            |                                                             =
=20
            |                                                             =
=20
     OFL_2  |                                                             =
=20
31 ---| |---+                                                             =
=20
            |                                                             =
=20
            |                                                             =
=20
            |                                                             =
=20
     OFL_3  |                                                             =
=20
32 ---| |---+


                                                                       =20
     IFL_31   IFL_32   OFL_32   IFL_30                              OFL_30=
=20
59 ---|\|------|\|------| |------| |---------------------------------( )---
     1-16     17-29    LATCH    OPERATOR                            RST OK=
=20
     RESET    RESET             RESET                                   =20
                                                                          =
=20
                                                                          =
=20
60                                                                        =
=20
                                                                          =
=20
                                                                          =
=20
  =20

                                                                       =20
     OFL_30                                                         OFL_32=
=20
61 ---| |---------------------------------------------------------+--(U)---
     RST OK                                                       | LATCH =
=20
                                                                  |       =
=20
                                                                  |       =
=20
                                                                  | OFL_1 =
=20
62                                                                +--(U)---
                                                                  |       =
=20
                                                                  |       =
=20
                                                                  |       =
=20
                                                                  | OFL_2 =
=20
63                                                                +--(U)---
                                                                  |       =
=20
                                                                  |       =
=20
                                                                  |       =
=20
                                                                  | OFL_3 =
=20
64                                                                +--(U)---



--=20
Patron saints in general are broadband connections to the Almighty
- Michelle Delio, Wired News
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             http://www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: